Permit: TC-MDP-0925-00525
Parcel: 141156800

Addresses:

9973 E LEBARON DR

Inspection Details

Date Description Inspector Status Comments
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Re-inspection required 6/9/26: 3/4" or larger hot water lines required to be insulated, seal penetration through top plate throughout, properly support line-set in attic, properly support all bathroom exhaust flex, properly seal vapor barrier at throughout, torn duct flex sheathing must be fixed, properly secure pex in wall at south coat closet in hall.