Permit: TC-COM-0624-01123
Parcel: 115180220

Addresses:

1501 N ORACLE RD

Inspection Details

Date Description Inspector Status Comments
COT - HCPL - Plumbing Final Re-inspection required 11/4/26: 14th floor corridor + electrical/storage rooms final walk: Existing Electrical room - 1. Identify Romex line in existing panel 2. Mark existing electrical panel schedule West mechanical room - 1. Clamps on unistrut above fan coil 2. HVAC refrigerant line supports 3. Conduit supports 4. Verify and label breaker for disconnect 5. Tie in overflow switch on fan coil IDF room - 1. Supports on conduits within 3' 2. Remove low voltage from fire sprinkler pipe Elevator lobby Electrical - 1. Mc clamps 2. Mark electrical panel 3. Clamps off of light Janitors closet - 1. Clamp temporary water lines East Main Electrical room - 1. MC clamps 2. Verify disconnect 3. Remove unused conduit East Existing Electrical room - 1. Replace knockouts on box 2. Relabel panel schedule