Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T22DV03141
Case Details
Entered Date:
05/25/2022
Applicant:
TUCSON ARIZONA PARTNERS LLC
Description:
TFD EMERGENCY CALL OUT
Completed Inspections
Case Status: COMPLIAN
Case Number: T22DV03141
Case Description: EMERGENCY
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/25/2022 | INSP - INITIAL CODE ENFORCMENT | TIDWELL | Approved | : EMERGENCY CALL OUT BY TFD: THERE WAS AN EXTERIOR FIRE TO THE THE OUTSIDE TRASH COMPACTOR. THE HEAT FROM THE FIRE CAUSED THE SPRINKLER TO DISCHARGE INSIDE THE BUILDING, EFFECTING THE STORE ROOM. THERE IS WATER INTRUSION ON THE FLOORING, INSIDE THE STRUCTURE. THE WATER EXPELLED INTO THE FLOOR OF THE MAIN SHOPPING AREA. ELECTRICAL: THERE IS A LIGHT FIXTURES EFFECTED BY WATER DISCHARGE IN THE STORE ROOM FROM THE SPRINKLER SYSTEM. CIRCUIT BREAKER 4 SHALL REMAIN OFF AT PANEL LP-1. PLUMBING: N/A MECHANICAL: WATER INTRUSION REMARKS: WALGREENS SHALL REMAIN CONDEMNED UNTIL THE SPRINKLER SYSTEM IS CHARGED, THE LIGHT FIXTURE IS REPAIRED BY AN LICENSED ELECTRICIAN TO ENSURE ALL ELECTRICAL DEVICES ARE SAFE TO REENERGIZE. AT THAT POINT THE STORE MY RE -OPEN. BETH TIDWELL 5/25/22 |
05/29/2022 | INSP - FOLLOW UP CODE ENFORCE | VALDEZ | Approved | DOC LOAD ONTO ONBASE CLOSE CASE |
Completed Activity Special Conditions
Case Description - EMERGENCY
Case Number - T22DV03141
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 6
Date | Name |
05/29/2022 | CONTACTED BY PHONE |
05/25/2022 | CONTACTED IN PERSON |
05/25/2022 | NOTICE AND ORDER ISSUED |
05/29/2022 | VIOLATION CLOSED |
05/25/2022 | STRUCTURE SECURED BY ??? |
05/25/2022 | CALLBACK |