Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
Case Number - T22DV03141
Inspection Description - INSP - INITIAL CODE ENFORCMENT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/25/2022 | INSP - INITIAL CODE ENFORCMENT | Approved | : EMERGENCY CALL OUT BY TFD: THERE WAS AN EXTERIOR FIRE TO THE THE OUTSIDE TRASH COMPACTOR. THE HEAT FROM THE FIRE CAUSED THE SPRINKLER TO DISCHARGE INSIDE THE BUILDING, EFFECTING THE STORE ROOM. THERE IS WATER INTRUSION ON THE FLOORING, INSIDE THE STRUCTURE. THE WATER EXPELLED INTO THE FLOOR OF THE MAIN SHOPPING AREA. ELECTRICAL: THERE IS A LIGHT FIXTURES EFFECTED BY WATER DISCHARGE IN THE STORE ROOM FROM THE SPRINKLER SYSTEM. CIRCUIT BREAKER 4 SHALL REMAIN OFF AT PANEL LP-1. PLUMBING: N/A MECHANICAL: WATER INTRUSION REMARKS: WALGREENS SHALL REMAIN CONDEMNED UNTIL THE SPRINKLER SYSTEM IS CHARGED, THE LIGHT FIXTURE IS REPAIRED BY AN LICENSED ELECTRICIAN TO ENSURE ALL ELECTRICAL DEVICES ARE SAFE TO REENERGIZE. AT THAT POINT THE STORE MY RE -OPEN. BETH TIDWELL 5/25/22 |