Case: T19DV06611
Case Details
Entered Date:
08/20/2019
Applicant:
IRVINGTON MEADOWS LLC
Description:
electrical outlets don't hold plugged in items outlets spark in the living room bed room and kitchen when plugging items in a/c keeps running does not stop running
Case Violations
Case Number: T19DV06611
Case Status: COMPLIAN
Case Description: RES: MINIMUM HOUSING
Total Violations: 7
Violation Date | Code Statue |
---|---|
11/07/2019 | REFERENCE |
11/07/2019 | T.C. Ch. 16, Sec. 16-11(b) (2) COOLING. Every dwelling unit, guest room, and congregate residence shall be provided, in at least one habitable room, with either mechanical cooling or an alternate cooling method. Cooling facilities shall be installed and maintained in a safe condition and in accordance with the manufacturer's recommendations, and shall be capable of providing adequate cooling, appropriate for the climate, to assure a safe living environment. Evaporative cooling shall be maintained to be free of excessive rust, corrosion or mineral deposits that limit proper operation. Any mounting apparatus for a cooling facility must be structurally sound. Mechanical fans or portable evaporative cooling devices may only be used on a temporary basis as the sole source of cooling when the permanent cooling system is being repaired or replaced. |
11/07/2019 | T.C. Ch. 16, Sec. 16-11(c) ELECTRICAL SYSTEM. (1) All dwellings and dwelling units shall be provided with electrical service. Electrical facilities connected to or in any building or structure are to be maintained hazard-free and in a state of good repair. The electrical system shall be free from such hazards as bare wiring; overloaded circuits or services; equipment not properly grounded; over-fused circuits; misuse of wiring, including the use of extension cords in lieu of permanent wiring; non-approved wiring; and wiring exposed to moisture or extreme heat. Broken, loose, frayed, inoperable, defective or missing portions of the electrical service, lines, switches, outlets, fixtures and fixture coverings shall be repaired or replaced. (2) All electrical equipment, wiring and appliances shall be installed and maintained in a safe manner and in accordance with all applicable laws. |
11/07/2019 | T.C. Ch. 16, Sec. 16-11(e) PLUMBING SYSTEMS. (3) All plumbing systems are to be maintained safe and hazard free and in a state of good repair. Every dwelling or dwelling unit shall have an adequate potable water supply. Every plumbing fixture, water and waste-pipe, and gas connection shall be properly installed in accordance with all applicable laws and maintained in good and sanitary working condition so as to prevent structural deterioration or health hazards, and are to be free from leaks and obstructions. |
11/07/2019 | T.C. Ch. 16, Sec. 16-11(f)(5) All interior coverings, finishes, surfaces including walls, ceilings and floors shall be maintained in a good, clean and sanitary condition. Peeling, chipping, flaking or abraded paint shall be repaired, removed or covered. All walls, ceilings or floors shall be free from holes, breaks and loose or rotting materials. Cracked or loose plaster, wallboard, decayed wood or other defective surface conditions shall be corrected. |
11/07/2019 | T.C. Ch. 16, Sec. 16-11(f)(6) All repair work shall be done in a workman like manner. |
11/07/2019 | T.C. Ch. 16, Sec. 16-11(h) INTERIOR INSECT AND RODENT CONTROL. The interior of all buildings and structures shall be kept free from infestation of insects, rodents and other noxious pests where such infestation threatens the health, safety or welfare of a person or persons. |
Outstanding Inspections
Case Number: T19DV06611
Case Status: COMPLIAN
Case Description: RES: MINIMUM HOUSING
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FOLLOW UP CODE ENFORCE | None | Not Inspected | ||
NPO(EL)-WIRING/SWITCH/OUTLT/FX | None | Not Inspected | ||
NPO(PL)-WATER HEATERS | None | Not Inspected | ||
NPO - INSECTS/PESTS | None | Not Inspected | ||
NPO - INT. BUILDING MAINTENANC | None | Not Inspected |
Completed Inspections
Case Status: COMPLIAN
Case Number: T19DV06611
Case Description: RES: MINIMUM HOUSING
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/07/2019 | INSP - INITIAL CODE ENFORCMENT | MENDOZA | Approved | ELECTRICAL OUTLETS IN THE LIVING ROOM POSSIBLY HAVE LOOSE WIRING. OPERATES INTERMITENT WHILE TESTING. TESTED AS OPEN GROUND, ONE WALL COMPLETELY INOPERABLE BEDROOM OUTLET BELOW LIGHT TESTS AS REVERSED AND LIGHT SHUTS OFF WHEN OUTLET IS USED. THIS POSES A FIRE HAZARD AND POSSIBLE DAMAGE TO EQUIPMENT THAT MAY BE CONNECTED TO IT. WATER HEATER INSTALLED WITHOUT PROPER TRPV DRAIN PIPE AND PAN. SUBSTANDARD WALL REPAIR IN THE KITCHEN AND ABUTTING WALL IN THE BATHROOM. ROACH INFESTATION SEEN WHILE CONDUCTING INSPECTION AIR HANDLER LACKS AIR FILTER AND UNIT IS EXTREMELY DIRTY. DIRT AND GRIME ALMOST COMPLETELY COVERING THE MOTOR POSING A FIRE HAZARD |
Completed Activity Special Conditions
Case Description - RES: MINIMUM HOUSING
Case Number - T19DV06611
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 5
Date | Name |
11/12/2019 | CONTACTED BY PHONE |
11/07/2019 | CONTACTED BY MAILING |
11/07/2019 | CONTACTED BY EMAIL |
11/07/2019 | NOTICE OF VIOLATION ISSUED |
12/10/2019 | VIOLATION CLOSED |