Case: T17DV04584
Case Details
Entered Date:
09/15/2017
Applicant:
LEAL STEVEN C
Description:
COMMUNICATION CALLED THE T.F.D. ON SITE WITH A BUILDING FIRE
Outstanding Inspections
Case Number: T17DV04584
Case Status: COMPLIAN
Case Description: EMERGENCY
Total Outstanding Inspections - 11
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/15/2017 | EMERGENCY CALL OUT | VIDAL | Item initialized | |
| 09/15/2017 | NPO(EL)-MAIN/PANEL/SUB/DISCONT | VIDAL | Item initialized | |
| 09/15/2017 | NPO(EL)-WIRING/SWITCH/OUTLT/FX | VIDAL | Item initialized | |
| 09/15/2017 | NPO(PL)-GAS SUPPLY/CONNECT | VIDAL | Item initialized | |
| 09/15/2017 | NPO(PL)-WATER HEATERS | VIDAL | Item initialized | |
| 09/15/2017 | NPO - EGRESS | VIDAL | Item initialized | |
| 09/15/2017 | NPO - SMOKE ALARMS | VIDAL | Item initialized | |
| 09/15/2017 | NPO - OTHER | VIDAL | Item initialized | |
| 09/15/2017 | NPO - EXT. BUILDING MAINTENANC | VIDAL | Item initialized | |
| 09/15/2017 | NPO - WORK WITHOUT PERMIT | VIDAL | Item initialized | |
| 09/15/2017 | NPO - INT. BUILDING MAINTENANC | VIDAL | Item initialized |
Completed Inspections
Case Status: COMPLIAN
Case Number: T17DV04584
Case Description: EMERGENCY
Total Completed Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/15/2017 | INSP - INITIAL CODE ENFORCMENT | VIDAL | Approved | Communication called that T.F.D. on site with a building fire. Arrived and the units were looking for hot spots and the fire investigators looking for cause. The fire was on the east building on the property on the east side at the top of the wall in the attic space area. There was electrical in the area and all the wiring was damaged by the fire. Had a 2" conduit on the exterior of the building at the top and that has fallen due to the unistrut has come loose and not able to stay on the wall. The metal security doors were forced opened and one was damaged and was boarded up by the owner. The wires were cut at the pole due to the amount of damage to the electrical wiring in the attic area. The fire did not come past the ceiling line through out. The wood trusses had metal corrigated iron on the roof on 1x ribbons or nailers. The gas meter has been removed prior to the fire and was capped on the riser on the east side of the property. The owner did show to the property and signed the paperwork and got the renter to have the building secured. Did the posting of Do Not Enter on the plywood covering the doorway. Did call Rick Hollander to look at the electrical due to was removing the electrical to the front unit and was not attached the structure that burned. T.E.P. call a designer to look at the electrical system due to the way the power was connected. Will check in 30 days. RV. |
| 09/15/2017 | INSP - INITIAL CODE ENFORCMENT | HOLLANDER | Approved | Was called fro electrical assist. Found Main Service feeders and conduits severly damaged by fire. Supports only held by drywall screws. Second Primary ran back to rear structure not code compliant. Service drop to low, meter socket not to standard, exposed conductors. Service for the two rear building appears undersized. Third building feed from second building is a 100 amp service with no mian disconnecting means from a 60 amp panel 30 amp single pole breaker. TEP cut and removed service conductors to all units. |
| 02/07/2018 | INSP - FOLLOW UP CODE ENFORCE | VIDAL | Approved | The building was vacant and secured and no work has been done. At this time the case will be closed per the administrator Rick Saldate due to working with the insurance. Violation Abated, Close Case. RV. |
Completed Activity Special Conditions
Case Description - EMERGENCY
Case Number - T17DV04584
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 2
| Date | Name |
| 09/15/2017 | NOTICE OF VIOLATION ISSUED |
| 09/15/2017 | STRUCTURE SECURED BY ??? |