Case: T17DV03150
Case Details
Entered Date:
07/21/2017
Applicant:
PRISM HOLDINGS LLC ATTN: MARTIN KALWAY
Description:
APPLIANCES OUTSIDE ATRIUM AREA MAY BE AN ELECTRICAL HAZARD WITH RAINS THAT LEAD TO FLOODING OUTSIDE OF THIS APARTMENT
Case Violations
Case Number: T17DV03150
Case Status: COMPLIAN
Case Description: RES: MINIMUM HOUSING
Total Violations: 2
Violation Date | Code Statue |
---|---|
08/08/2017 | T.C. Ch. 16, Sec. 16-11(c) ELECTRICAL SYSTEM. (1) All dwellings and dwelling units shall be provided with electrical service. Electrical facilities connected to or in any building or structure are to be maintained hazard-free and in a state of good repair. The electrical system shall be free from such hazards as bare wiring; overloaded circuits or services; equipment not properly grounded; over-fused circuits; misuse of wiring, including the use of extension cords in lieu of permanent wiring; non-approved wiring; and wiring exposed to moisture or extreme heat. Broken, loose, frayed, inoperable, defective or missing portions of the electrical service, lines, switches, outlets, fixtures and fixture coverings shall be repaired or replaced. (2) All electrical equipment, wiring and appliances shall be installed and maintained in a safe manner and in accordance with all applicable laws. |
08/08/2017 | T.C. Ch. 16, Sec. 16-11(e) PLUMBING SYSTEMS. (3) All plumbing systems are to be maintained safe and hazard free and in a state of good repair. Every dwelling or dwelling unit shall have an adequate potable water supply. Every plumbing fixture, water and waste-pipe, and gas connection shall be properly installed in accordance with all applicable laws and maintained in good and sanitary working condition so as to prevent structural deterioration or health hazards, and are to be free from leaks and obstructions. |
Outstanding Inspections
Case Number: T17DV03150
Case Status: COMPLIAN
Case Description: RES: MINIMUM HOUSING
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/28/2017 | NPO(EL)-WIRING/SWITCH/OUTLT/FX | MENDOZA | Item closed | |
08/28/2017 | NPO - EXT. HAZ/ATTRACT NUISANC | MENDOZA | Item closed |
Completed Inspections
Case Status: COMPLIAN
Case Number: T17DV03150
Case Description: RES: MINIMUM HOUSING
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/08/2017 | INSP - INITIAL CODE ENFORCMENT | MENDOZA | Approved | TWO WASHERS, TWO DRYERS AND AN ELECTRIC WATER HEARTER UNER THE STAIRWAY AT THE SOUTHWEST CORNER OF THE COMPLEX. DRYERS CIRCUITS APPEAR TO BE PROPER WIRED, ELECTRICAL PANEL SHOWED NO DEFICIENCIES. WASHER/ELECTRIC WATER HEATER PANEL IS MISSING THE DEAD FRONT. ONE BREAKER IS DOUBLE LUGGED. GROUNDS AND NEUTRALS ARE CONNECTED TO THE SAME BUS BAR. CONDUIT UNDER THE PANEL IS DISCONNECTED EXPOSING THE WIRES. WATER HEATER WIRING IS NOT SECURED/PROTECTED AT THE WATER HEATER. WIRING IS NOT RATED FOR OUTDOOR USE AND IS NOT WITHIN CONDUIT IS PLUGGED INTO THE SAME CIRCUIT AS THE WASHERS. TPRV VALVE IS EXTREMELY CORRODED AND MISSING THE DRAIN PIPE. OPEN LIGHT FIXTURE CIRCUIT ON CEILING ABOVE THE APPLIANCES. |
08/28/2017 | INSP - FOLLOW UP CODE ENFORCE | MENDOZA | Approved | PANEL FOR WASHERS/DRYERS AND WATER HEATER REPLACED. ALL CIRCUITS PROPER SIZE WITH EXTERIOR COVERS AT THE OUTLETS. WATER HEATER PROPERLY INSTALLED AND CONNECTED TO THE NEW PANEL. GROUNDS AND NEUTRALS CONNECTED PROPERLY AS WELL AS ALL OVERCURRENT PROTECTION. |
Completed Activity Special Conditions
Case Description - RES: MINIMUM HOUSING
Case Number - T17DV03150
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 3
Date | Name |
08/08/2017 | CONTACTED BY MAILING |
08/08/2017 | NOTICE OF VIOLATION ISSUED |
08/28/2017 | VIOLATION CLOSED |