Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
Case Number - T17DV03150
Inspection Description - INSP - INITIAL CODE ENFORCMENT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/08/2017 | INSP - INITIAL CODE ENFORCMENT | Approved | TWO WASHERS, TWO DRYERS AND AN ELECTRIC WATER HEARTER UNER THE STAIRWAY AT THE SOUTHWEST CORNER OF THE COMPLEX. DRYERS CIRCUITS APPEAR TO BE PROPER WIRED, ELECTRICAL PANEL SHOWED NO DEFICIENCIES. WASHER/ELECTRIC WATER HEATER PANEL IS MISSING THE DEAD FRONT. ONE BREAKER IS DOUBLE LUGGED. GROUNDS AND NEUTRALS ARE CONNECTED TO THE SAME BUS BAR. CONDUIT UNDER THE PANEL IS DISCONNECTED EXPOSING THE WIRES. WATER HEATER WIRING IS NOT SECURED/PROTECTED AT THE WATER HEATER. WIRING IS NOT RATED FOR OUTDOOR USE AND IS NOT WITHIN CONDUIT IS PLUGGED INTO THE SAME CIRCUIT AS THE WASHERS. TPRV VALVE IS EXTREMELY CORRODED AND MISSING THE DRAIN PIPE. OPEN LIGHT FIXTURE CIRCUIT ON CEILING ABOVE THE APPLIANCES. |