Case: T16DV00557
Case Details
Entered Date:
02/05/2016
Applicant:
PAG DESERT BREEZE LLC 3 / HMB PROPERTIES: REGISTERED AGENT: KERRY BROOKS
Description:
ELECTRICAL VIOLATIONSIN THE ENTIRE PARK
Case Violations
Case Number: T16DV00557
Case Status: COMPLIAN
Case Description: MULTIPLE TYPES
Total Violations: 1
Violation Date | Code Statue |
---|---|
03/03/2016 | T.C. Ch. 16, Sec. 16-4. PERMITS REQUIRED. Unless otherwise exempt pursuant to section 301 of the Administrative Code, as adopted by reference per section 6-1 of this Code, or pursuant to any other ordinance or statute, no building, structure or building service equipment regulated by this chapter or by the technical codes adopted by the city shall be built, erected, constructed, enlarged, altered, repaired, moved, improved, removed, converted or demolished unless a permit first has been obtained from the building official in the manner provided in the administrative and building codes adopted by the city. The purpose of a permit is to ensure that all construction is inspected by qualified City of Tucson personnel as directed by ordinance to verify compliance with city codes. Failure to obtain proper permit with inspections and approvals shall deem the construction to be unsafe. |
Outstanding Inspections
Case Number: T16DV00557
Case Status: COMPLIAN
Case Description: MULTIPLE TYPES
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/16/2016 | NPO(EL)-MAIN/PANEL/SUB/DISCONT | VALDEZ | Extension granted | |
08/16/2016 | NPO(EL)-WIRING/SWITCH/OUTLT/FX | VALDEZ | Extension granted |
Completed Inspections
Case Status: COMPLIAN
Case Number: T16DV00557
Case Description: MULTIPLE TYPES
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/04/2016 | INSP - INITIAL CODE ENFORCMENT | VALDEZ | Approved | THE PARKS MASTER METERED SYSTEM HAS TWO SERVICE LOCATIONS. ONE OF THE PARK'S SERVICE LOCATIONS IS NEXT TO THE LAUNDRY ROOM. THIS SERVICE HAS MULTIPLE DISCONNECTS ALONG WITH A GUTTER BOX WITH MISSING HARDWARE. THIS EQUIPMENT IS BEING SUPPORTED BY A DILAPIDATED AND DETERIORATING FREE STANDING WOOD FRAMED/ POST STRUCTURE. ADDITIONAL SUPPORT METHODS HAVE BEEN IMPLEMENTED TO PROVIDE STABILITY TO THE DETERIORATED AND DILAPIDATED STRUCTURE, ALL THESE SUPPORT METHODS ARE FAILING ONE OF THE POSTS IS SO DETERIORATED DUE TO WOOD TO EARTH CONTACT. ALL THREE POSTS ARE FAILING TO SUPPORT THE ELECTRICAL EQUIPMENT. THE ENTIRE STRUCTURE HAS LEANED OVER TO ONE SIDE. THE WOOD CABINETRY WAS DESIGNED AS AN ENCLOSURE TO THE ELECTRICAL SYSTEM AND NOW IS SO DILAPIDATED IT NO LONGER PROVIDES PROTECTION TO THE EQUIPMENT. THE ELECTRICAL EQUIPMENT HAS SIGNS OF DETERIORATION THERE IS RUST ON THE EXTERIOR AND REAR OF THE DISCONNECTS WHICH IS PREVENTING AN EFFECTIVE AND SAFE GROUND FAULT PATH TO EARTH. THE ELECTRICAL METAL CONDUITS WHICH RUNS FROM THE EQUIPMENT TO UNDERGROUND IS UNDER A GREAT DEAL OF STRESS DUE TO THE FAILING WOOD SUPPORT SYSTEM LEANING OVER. THE CONDUIT IS AIDING IN SUPPORTING THE ENTIRE ELECTRICAL SYSTEM AND THE WOOD STRUCTURE. THE ELECTRICAL PANEL CIRCUIT DIRECTORY IS NOT LEGIBLE OR DISTINGUISHABLE FROM ONE ANOTHER FOR PROPER LABELING. THERE ARE CLEARANCE VIOLATIONS. RUST IS PRESENT ON TERMINAL LUGS WHICH HAVE RENDERED THEM BEYOND USABILITY. THERE ARE MULTIPLE WIRE TERMINATIONS IN THE SAME TERMINAL LUG. THE DOOR TO ONE OF THE DISCONNECTS CAN NOT FULLY OPEN. THE CURRENT PLACEMENT OF THE STRUCTURE ALSO BLOCKS THE PANEL TO THE LAUNDRY ROOM THERE IS NO ACCESS. THE SECOND SERVICE EQUIPMENT IS A 200 AMP SERVICE. THE LOCATION IS IN SPACE 10 NORTH OF THE PARK. THIS SERVICE WAS DAMAGE BY FIRE AND IS A TOTAL LOSS. NOTE: THE MANUFACTURES INSTRUCTIONS ARE NOT PRESENT OR UNREADABLE AT THE SERVICE DISCONNECTS AND THE DISCONNECTING MEANS. THE DISCONNECTING MEANS TO THE MOBILE HOMES UNIT 1 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS NO GROUNDING ELECTRODE SYSTEM THE CONDUIT IS NOT PROPERLY SUPPORTED. THE SUPPORT SYSTEM HAS A BROKEN WOOD POST ALL ELECTRICAL EQUIPMENT IS UNSTABLE AND NOT PROPERLY SUPPORTED. UNIT 2 100 AMP FUSE TYPE DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS MULTIPLE WIRE TERMINATIONS IN THE SAME TERMINAL LUG VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE THE SUPPORT SYSTEM HAS A BROKEN WOOD POST. ALL ELECTRICAL EQUIPMENT IS UNSTABLE AND NOT PROPERLY SUPPORTED. UNIT 3 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS NO GROUNDING ELECTRODE SYSTEM, UNUSED OPENINGS. THE WOOD SUPPORT SYSTEM IS UNSTABLE AND DETERIORATED. ALL ELECTRICAL EQUIPMENT IS UNSTABLE AND NOT PROPERLY SUPPORTED. THE CONDUIT NOT PROPERLY INSTALLED AND SUPPORTED. UNIT 4 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE. MULTIPLE WIRE TERMINATIONS IN THE SAME TERMINAL LUG PROPERLY SECURE CONDUIT TO THE DISCONNECT, MISSING FITTING. UNIT 5 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS UNUSED OPENINGS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE. THE NEUTRALS AND GROUNDS ARE NOT SEPARATED THERE ARE EXPOSED AND UNPROTECTED CONDUCTORS FROM THE METER TO THE DISCONNECT. UNIT 6 60 AMP DISCONNECT MEANS THE POWER SUPPLY CORD IS 50 AMPS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS NO DEAD FRONT VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE. THE NEUTRALS AND GROUNDS ARE NOT SEPARATED THE POWER SUPPLY CORD HAS EXPOSED CONDUCTORS DUE TO MISSING INSULATION. THE SUPPORT SYSTEM HAS A BROKEN WOOD POST. ALL ELECTRICAL EQUIPMENT IS UNSTABLE AND NOT PROPERLY SUPPORTED. UNAPPROVED HARDWARE (LAG BOLT) SUPPORTING THE BREAKER. UNIT 7 60 AMP DISCONNECTING MEANS HARD WIRED THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS NO GROUNDING ELECTRODE SYSTEM JUNCTION BOX HAS A BROKEN WOOD POST THERE ARE EXPOSED CONDUCTORS UNAPPROVED WIRING METHODS IMPROPER SPLICED CONNECTIONS UNIT8 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS NO DEAD FRONT, NO GROUNDING ELECTRODE SYSTEM METER NIPPLE BROKEN THE SUPPORT SYSTEM HAS A BROKEN WOOD POST. ALL ELECTRICAL EQUIPMENT IS UNSTABLE AND NOT PROPERLY SUPPORTED. MISSING COVER ON THE POWER SUPPLY RECEPTACLE ENCLOSURE. UNIT 9 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS NO GROUNDING ELECTRODE SYSTEM UNIT 10 THIS IS THE FIRE DAMAGED UNIT. THE 200 AMP SERVICE AND THE UNIT'S DISCONNECTING MEANS HAVE BURNT AND ARE NO LONGER SERVICEABLE AND SUITABLE FOR USE. THIS FIRE DAMAGED EQUIPMENT MUST BE REMOVED. UNIT 11 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS NO GROUNDING ELECTRODE SYSTEM, UNUSED OPENINGS THE POWER SUPPLY CORD HAS EXPOSED CONDUCTORS BETWEEN THE CORD AND THE CORD CAP. UNIT 12 50 AMP DISCONNECTING MEANS THE POWER SUPPLY CORD HAS EXPOSED CONDUCTORS BETWEEN THE CORD AND THE CORD CAP THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS NO GROUNDING ELECTRODE SYSTEM UNSECURED POWER SUPPLY RECEPTACLE UNIT 13 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING OF DISCONNECTING MEANS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE. UNIT 14 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE THE POWER SUPPLY CORD IS RATED AT 30 AMPS. PALLET FENCE IS OBSTRUCTING THE WORKING CLEARING THE POWER SUPPLY CORD HAS EXPOSED CONDUCTORS BETWEEN THE CORD AND THE CORD CAP UNIT 15 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS NO DEAD FRONT VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE UNIT 16 UNABLE TO DETERMINE AMPACITY THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS DISCONNECTING MEANS HAS MISSING FUSE HOLDER VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE UNIT 17 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS THE POWER SUPPLY CORD HAS EXPOSED CONDUCTORS BETWEEN THE CORD AND THE CORD CAP 50 AMP RECEPTACLE IS CRACKED VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE UNIT 18 THE DISCONNECTING MEANS IS A PANEL BOARD WITH DUAL POLE 30 AMP BREAKER AND (3) 20 AMP BREAKERS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS NO DEAD FRONT NEUTRALS AND GROUNDS ARE NOT SEPARATED VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE UNIT 19 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE UNIT 20 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS 50 AMP RECEPTACLE IS CRACKED VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE UNIT 21 30 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS UNSECURED POWER SUPPLY RECEPTACLE VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE UNIT 22 30 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS UNSECURED POWER SUPPLY RECEPTACLE VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE POWER SUPPLY RECEPTACLE POST IS BROKEN. UNIT 23 30 AMP DISCONNECTING MEANS UNUSED OPENINGS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE THE GROUNDING ELECTRODE CONDUCTOR HAS MULTIPLE TERMINATIONS AT THE ACORN CLAMP UNIT 24 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE THE GROUNDING ELECTRODE CONDUCTOR HAS MULTIPLE TERMINATIONS AT THE ACORN CLAMP UNIT 25 50 AMP DISCONNECTING MEANS UNUSED OPENINGS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE THE GROUNDING ELECTRODE CONDUCTOR HAS MULTIPLE TERMINATIONS AT THE ACORN CLAMP UNIT 26 80 AMP DISCONNECTING MEANS HARDWIRED THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS NEUTRAL NOT CONNECTED UNAPPROVED WIRING METHODS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE UNIT 27 50 AMP DISCONNECTING MEANS UNUSED OPENINGS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE NEUTRALS AND GROUNDS ARE NOT SEPARATED MULTIPLE WIRE TERMINATIONS IN THE SAME TERMINAL LUG UNAPPROVED WIRING METHODS ON AN ADDITIONAL CIRCUIT WHICH IS MADE UP OF AN EXTENSION CORD RUNNING INSIDE PEX TUBING UNIT 28 40 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE UNIT 29 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE THE GROUNDING ELECTRODE CONDUCTOR HAS MULTIPLE TERMINATIONS AT THE ACORN CLAMP UNIT 30 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE THE GROUNDING ELECTRODE CONDUCTOR HAS MULTIPLE TERMINATIONS AT THE ACORN CLAMP LAUNDRY ROOM UNABLE TO INSPECT NO ACCESS TO THE EXTERIOR PANEL IT IS BEING OBSTRUCTED BY THE COOLER'S WOOD FRAMED STAND AND THE MAIN SUPPORT SYSTEM TO THE MAIN SERVICE. UNIT 31 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE UNIT 32 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE UNIT 33 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS THE RECEPTACLE SUPPORT POST IS BROKEN VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE UNIT 34 50 AMP DISCONNECTING MEANS HARDWIRED THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE UNIT 35 30 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE UNIT 36 30 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE UNIT 37 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE UNIT 38 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE UNIT 39 60 AMP DISCONNECTING MEANS RECEPTACLE IS RATED AT 50 AMPS, THE OVER CURRENT PROTECTION IS OVER SIZED FOR ALL DOWN STREAM DEVICES AND USE. UNUSED OPENINGS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE NEUTRALS AND GROUNDS ARE NOT SEPARATED UNIT 40 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE UNIT 41 65 AMP DISCONNECTING MEANS UNUSED OPENINGS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS MISSING POWER SUPPLY RECEPTACLE INSIDE THE ENCLOSURE VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE UNIT 42 30 AMP SINGLE POLE BREAKER IS THE DISCONNECTING MEANS. THERE ALSO IS (2) 20 AMP CIRCUIT BREAKERS IN THE PANEL THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE THERE IS EXPOSED UNPROTECTED UF CABLE COMING FROM THE EARTH THE POWER SUPPLY RECEPTACLE ENCLOSURE IS IN LOT 42 UNABLE TO INSPECT. UNIT 43 UNABLE TO INSPECT NO ACCESS UNIT 44 UNABLE TO DETERMINE AMPACITY THE DISCONNECT HAS MISSING INTERNAL COMPONENTS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS NO DEAD FRONT USED OPENINGS NO GROUNDING ELECTRODE SYSTEM UNIT 45 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE UNAPPROVED WIRING METHODS NEUTRALS AND GROUNDS ARE NOT SEPARATED UNIT 46 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS NO GROUNDING ELECTRODE SYSTEM EXPOSED UNPROTECTED FEEDERS COMING FROM THE EARTH UNIT 47 30 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS NO GROUNDING ELECTRODE SYSTEM EXPOSED CONDUCTORS THE METER IS NOT PROPERLY SECURED UNIT 48 UNABLE TO INSPECT NO ACCESS UNIT 49 UNABLE TO INSPECT NO ACCESS UNIT 50 30 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS WORK CLEARANCE, EQUIPMENT IS UNDER A COOLER STAND NO ACCESS NON SHEATHED METALLIC CABLE RUNS UNDERGROUND NO GROUNDING ELECTRODE SYSTEM THE SUPPORT SYSTEM HAS A BROKEN WOOD POST. ALL ELECTRICAL EQUIPMENT IS UNSTABLE AND NOT PROPERLY SUPPORTED UNIT 51 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS MISSING DEAD FRONT UNUSED OPENINGS EXPOSED CONDUCTORS WORK CLEARANCE IS BEING OBSTRUCTED BY A WATER PIPE AND A GAS METER. VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE LOOSE WOOD SUPPORT POST THERE ARE 250 AMP FUSES IN THE DISCONNECT AT THIS LOCATION VERIFY THE EQUIPMENT AND ITS USE. THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE LOOSE WOOD SUPPORT POST UNIT 52 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS UNUSED OPENINGS WORK CLEARANCE IS BEING OBSTRUCTED BY COOLER STAND NO GROUNDING ELECTRODE SYSTEM UNIT 53 50 AMP DISCONNECTING MEANS HARDWIRED NO DEAD FRONT ON RECEPTACLE ENCLOSURE THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS NO GROUNDING ELECTRODE SYSTEM UNIT 54 UNABLE TO DETERMINE AMPACITY OF FUSES UNREADABLE 50 AMP POWER SUPPLY CORD IS HARDWIRED TO THE DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS WORK CLEARANCE IS BEING OBSTRUCTED BY COOLER STAND VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE NEUTRAL IS NOT CONNECTED WATER TYPE PVC IS BEING USED AS CONDUIT UNIT 55 30 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS NO GROUNDING ELECTRODE SYSTEM CONDUIT NOT PROPERLY SECURED 50 AMP POWER SUPPLY RECEPTACLE HAS EXPOSED CONDUCTORS ALL ELECTRICAL EQUIPMENT ARE UNSTABLE AND NOT PROPERLY SUPPORTED TO WOOD STRUCTURE. UNIT 56 60 AMP DISCONNECTING MEANS HARDWIRED THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS TO A 125 AMP PANEL BOARD WHICH IS ATTACHED TO THE MOBILE HOME. WORK CLEARANCE THE WOOD POST, METER AND DISCONNECT ARE OBSTRUCTING THE PANEL BOARD VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE UNIT 57 UNABLE TO DETERMINE AMPACITY MISSING FUSE HOLDER THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS THE POWER SUPPLY CORD IS HARDWIRED MISSING ALL ELECTRICAL INTERNAL COMPONENTS OF THE DISCONNECT MEANS MISSING METER VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE EXPOSED CONDUCTORS THE SUPPORT SYSTEM HAS A BROKEN WOOD POST. ALL ELECTRICAL EQUIPMENT IS UNSTABLE AND NOT PROPERLY SUPPORTED UNIT 58 60 AMP DISCONNECTING MEANS THE POWER SUPPLY CORD IS HARDWIRED THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS NO GROUNDING ELECTRODE SYSTEM UNIT 59 30 AMP DISCONNECTING MEANS HARDWIRED THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS NO GROUNDING ELECTRODE SYSTEM WORK CLEARANCE IS BEING OBSTRUCTED BY THE MOBILE HOME EXPOSED UNPROTECTED FEEDERS COMING FROM THE EARTH IMPROPER SLICE CONNECTIONS ON THE FEEDERS UNIT 60 60 AMP DISCONNECTING MEANS THE OVER CURRENT PROTECTION IS OVER SIZED FOR ALL DOWN STREAM DEVICES AND USE. 50 AMP POWER SUPPLY CORD IS HARDWIRED THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS UNUSED OPENINGS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE UNIT 61 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS NO GROUNDING ELECTRODE SYSTEM NEUTRALS AND GROUNDS ARE NOT SEPARATED WORK CLEARANCE IS BEING OBSTRUCTED BY THE CHAIN LINK FENCE THE SUPPORT SYSTEM HAS IS DILAPIDATED AND NOT SECURE. ALL ELECTRICAL EQUIPMENT IS UNSTABLE AND NOT PROPERLY SUPPORTED UNIT 62 UNABLE TO DETERMINE AMPACITY OF THE DISCONNECT MEANS DUE TO WORK CLEARANCE IS OBSTRUCTED BY A 4X4 POST THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS NO GROUNDING ELECTRODE SYSTEM EXPOSED CONDUCTORS THE SUPPORT SYSTEM HAS IS DILAPIDATED AND NOT SECURE. ALL ELECTRICAL EQUIPMENT IS UNSTABLE AND NOT PROPERLY SUPPORTED UNIT 63 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE THE SUPPORT SYSTEM HAS IS DILAPIDATED AND NOT SECURE. ALL ELECTRICAL EQUIPMENT ARE UNSTABLE AND NOT PROPERLY SUPPORTED UNIT 64 60 AMP DISCONNECTING MEANS POWER SUPPLY CORD IS RATED AT 50 AMPS THE OVER CURRENT PROTECTION IS OVER SIZED FOR ALL DOWN STREAM DEVICES AND USE THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS UNUSED OPENINGS NO GROUNDING ELECTRODE SYSTEM EXPOSED CONDUCTORS WORK CLEARANCE IS OBSTRUCTED BY A WATER LINE UNIT 65 UNABLE TO DETERMINE AMPACITY OF THE DISCONNECT MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS NO GROUNDING ELECTRODE SYSTEM RECEPTACLE ENCLOSURE IS NOT PROPERLY SECURED WORK CLEARANCE IS OBSTRUCTED BY THE GAS METER UNIT 66 60 AMP DISCONNECTING MEANS POWER SUPPLY CORD IS RATED AT 30 AMPS RECEPTACLE IS RATED AT 50 AMPS THE OVER CURRENT PROTECTION IS OVER SIZED FOR ALL DOWN STREAM DEVICES AND USE NEUTRALS AND GROUNDS ARE NOT SEPARATED THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE THE SUPPORT SYSTEM HAS IS DILAPIDATED AND NOT SECURE. ALL ELECTRICAL EQUIPMENT IS UNSTABLE AND NOT PROPERLY SUPPORTED UNIT 67 THERE (2) 200 AMPS DISCONNECTS AND A FUSE TYPE OF DISCONNECTING MEANS WHICH I AM UNABLE TO DETERMINE THE AMPACITY OF THE DISCONNECT MEANS DUE TO UNREADABLE FUSES. EXPOSED UNPROTECTED FEEDERS COMING FROM THE EARTH THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE UNAPPROVED WIRING METHODS VERIFY ALL OF THE EQUIPMENT AND ITS USE. UNIT 68 60 AMP DISCONNECTING MEANS THE OVER CURRENT PROTECTION IS OVER SIZED FOR ALL DOWN STREAM DEVICES AND USE THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS NO GROUNDING ELECTRODE SYSTEM UNUSED OPENINGS EXPOSED CONDUCTORS THE POWER SUPPLY CORD HAS EXPOSED CONDUCTORS UNIT 69 60 AMP DISCONNECTING MEANS THE OVER CURRENT PROTECTION IS OVER SIZED FOR ALL DOWN STREAM DEVICES AND USE THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS WORK CLEARANCE IS BEING OBSTRUCTED BY A WOOD POST NO GROUNDING ELECTRODE SYSTEM THE SUPPORT SYSTEM HAS IS DILAPIDATED AND NOT SECURE. ALL ELECTRICAL EQUIPMENT IS UNSTABLE AND NOT PROPERLY SUPPORTED UNIT 70 50 AMP DISCONNECTING MEANS NEUTRALS AND GROUNDS ARE NOT SEPARATED THERE ALSO ANOTHER 30 AMP FUSE PANEL VERIFY ALL EQUIPMENT AND ITS USE THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE MULTIPLE WIRE TERMINATIONS IN THE SAME TERMINAL LUG THE SUPPORT SYSTEM HAS IS DILAPIDATED AND NOT SECURE. ALL ELECTRICAL EQUIPMENT IS UNSTABLE AND NOT PROPERLY SUPPORTED UNIT 71 UNABLE TO DETERMINE AMPACITY OF THE DISCONNECT MEANS DUE TO MISSING INTERNAL COMPONENTS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS NO POWER SUPPLY RECEPTACLE EQUIPMENT NO GROUNDING ELECTRODE SYSTEM UNIT 72 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS POWER SUPPLY CORD IS HARDWIRED NO GROUNDING ELECTRODE SYSTEM UNIT 73 60 AMP DISCONNECTING MEANS HARDWIRED THE OVER CURRENT PROTECTION IS OVER SIZED FOR ALL DOWN STREAM DEVICES AND USE. POWER SUPPLY CORD IS RATED AT 50 AMPS NO GROUNDING SYSTEM THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS RECEPTACLE ENCLOSURE IS NOT PROPERLY SECURED THE SUPPORT SYSTEM HAS IS DILAPIDATED AND NOT SECURE. ALL ELECTRICAL EQUIPMENT IS UNSTABLE AND NOT PROPERLY SUPPORTED UNIT 74 50 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS NO GROUNDING ELECTRODE SYSTEM UNAPPROVED WIRING METHODS MULTIPLE WIRE TERMINATIONS IN THE SAME TERMINAL LUG NO GROUNDING ELECTRODE SYSTEM EXPOSED UNPROTECTED FEEDERS THE SUPPORT SYSTEM HAS IS DILAPIDATED AND NOT SECURE. ALL ELECTRICAL EQUIPMENT IS UNSTABLE AND NOT PROPERLY SUPPORTED UNIT 75 UNABLE TO DETERMINE AMPACITY OF THE DISCONNECT MEANS NO GROUNDING ELECTRODE SYSTEM THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING OF DISCONNECTING MEANS UNIT 76 IS LOCATED SECOND ROW FROM THE NORTH SIDE OF THE PARK. 30 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS NEUTRALS AND GROUNDS ARE NOT SEPARATED NO DEAD FRONT EXPOSED CONDUCTORS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE THE POWER SUPPLY RECEPTACLE ENCLOSURE AND THE CONDUIT HAS BEEN DESTROYED UNIT 80 200 AMP DISCONNECTING MEANS THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE. |
08/12/2016 | INSP - FOLLOW UP CODE ENFORCE | VALDEZ | Approved | PERMIT T16CM05070 ISSUED ON 08-12-2016 AND EXPIRES ON 02-12-2016, CONTRACTOR IS WILL MC CLURE 520 308-6235 |
Completed Activity Special Conditions
Case Description - MULTIPLE TYPES
Case Number - T16DV00557
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 5
Date | Name |
02/12/2016 | CONTACTED BY PHONE |
02/18/2016 | CONTACTED IN PERSON |
03/04/2016 | CONTACTED BY MAILING |
02/12/2016 | CONTACTED BY EMAIL |
08/03/2017 | VIOLATION CLOSED |