Case: T16DV00557

Parcel: 140190080


Addresses:

5344 S PARK AV


Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Case Number - T16DV00557

Inspection Description - INSP - INITIAL CODE ENFORCMENT

Inspection Status - Approved

Date Description Inspector Results Comments
02/04/2016 INSP - INITIAL CODE ENFORCMENT Approved THE PARKS MASTER METERED SYSTEM HAS TWO SERVICE LOCATIONS.

ONE OF THE PARK'S SERVICE LOCATIONS IS NEXT TO THE LAUNDRY ROOM. THIS SERVICE HAS MULTIPLE DISCONNECTS ALONG WITH A GUTTER BOX WITH MISSING HARDWARE. THIS EQUIPMENT IS BEING SUPPORTED BY A DILAPIDATED AND DETERIORATING FREE STANDING WOOD FRAMED/ POST STRUCTURE. ADDITIONAL SUPPORT METHODS HAVE BEEN IMPLEMENTED TO PROVIDE STABILITY TO THE DETERIORATED AND DILAPIDATED STRUCTURE, ALL THESE SUPPORT METHODS ARE FAILING ONE OF THE POSTS IS SO DETERIORATED DUE TO WOOD TO EARTH CONTACT. ALL THREE POSTS ARE FAILING TO SUPPORT THE ELECTRICAL EQUIPMENT. THE ENTIRE STRUCTURE HAS LEANED OVER TO ONE SIDE. THE WOOD CABINETRY WAS DESIGNED AS AN ENCLOSURE TO THE ELECTRICAL SYSTEM AND NOW IS SO DILAPIDATED IT NO LONGER PROVIDES PROTECTION TO THE EQUIPMENT.

THE ELECTRICAL EQUIPMENT HAS SIGNS OF DETERIORATION
THERE IS RUST ON THE EXTERIOR AND REAR OF THE DISCONNECTS WHICH IS PREVENTING AN EFFECTIVE AND SAFE GROUND FAULT PATH TO EARTH. THE ELECTRICAL METAL CONDUITS WHICH RUNS FROM THE EQUIPMENT TO UNDERGROUND IS UNDER A GREAT DEAL OF STRESS DUE TO THE FAILING WOOD SUPPORT SYSTEM LEANING OVER.
THE CONDUIT IS AIDING IN SUPPORTING THE ENTIRE ELECTRICAL SYSTEM AND THE WOOD STRUCTURE.
THE ELECTRICAL PANEL CIRCUIT DIRECTORY IS NOT LEGIBLE OR DISTINGUISHABLE FROM ONE ANOTHER FOR PROPER LABELING.
THERE ARE CLEARANCE VIOLATIONS. RUST IS PRESENT ON TERMINAL LUGS WHICH HAVE RENDERED THEM BEYOND USABILITY. THERE ARE MULTIPLE WIRE TERMINATIONS IN THE SAME TERMINAL LUG.
THE DOOR TO ONE OF THE DISCONNECTS CAN NOT FULLY OPEN. THE CURRENT PLACEMENT OF THE STRUCTURE ALSO BLOCKS THE PANEL TO THE LAUNDRY ROOM THERE IS NO ACCESS.

THE SECOND SERVICE EQUIPMENT IS A 200 AMP SERVICE. THE LOCATION IS IN SPACE 10 NORTH OF THE PARK. THIS SERVICE WAS DAMAGE BY FIRE AND IS A TOTAL LOSS.

NOTE: THE MANUFACTURES INSTRUCTIONS ARE NOT PRESENT OR UNREADABLE AT THE SERVICE DISCONNECTS AND THE DISCONNECTING MEANS.





THE DISCONNECTING MEANS TO THE MOBILE HOMES

UNIT 1
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
NO GROUNDING ELECTRODE SYSTEM
THE CONDUIT IS NOT PROPERLY SUPPORTED.
THE SUPPORT SYSTEM HAS A BROKEN WOOD POST
ALL ELECTRICAL EQUIPMENT IS UNSTABLE AND NOT PROPERLY SUPPORTED.


UNIT 2
100 AMP FUSE TYPE DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
MULTIPLE WIRE TERMINATIONS IN THE SAME TERMINAL LUG
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE
THE SUPPORT SYSTEM HAS A BROKEN WOOD POST.
ALL ELECTRICAL EQUIPMENT IS UNSTABLE AND NOT PROPERLY SUPPORTED.

UNIT 3
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
NO GROUNDING ELECTRODE SYSTEM, UNUSED OPENINGS.
THE WOOD SUPPORT SYSTEM IS UNSTABLE AND DETERIORATED. ALL ELECTRICAL EQUIPMENT IS UNSTABLE AND NOT PROPERLY SUPPORTED.
THE CONDUIT NOT PROPERLY INSTALLED AND SUPPORTED.

UNIT 4
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE.
MULTIPLE WIRE TERMINATIONS IN THE SAME TERMINAL LUG
PROPERLY SECURE CONDUIT TO THE DISCONNECT, MISSING FITTING.






UNIT 5
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
UNUSED OPENINGS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE.
THE NEUTRALS AND GROUNDS ARE NOT SEPARATED
THERE ARE EXPOSED AND UNPROTECTED CONDUCTORS FROM THE METER TO THE DISCONNECT.

UNIT 6
60 AMP DISCONNECT MEANS
THE POWER SUPPLY CORD IS 50 AMPS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
NO DEAD FRONT
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE.
THE NEUTRALS AND GROUNDS ARE NOT SEPARATED
THE POWER SUPPLY CORD HAS EXPOSED CONDUCTORS DUE TO MISSING INSULATION.
THE SUPPORT SYSTEM HAS A BROKEN WOOD POST.
ALL ELECTRICAL EQUIPMENT IS UNSTABLE AND NOT PROPERLY SUPPORTED.
UNAPPROVED HARDWARE (LAG BOLT) SUPPORTING THE BREAKER.

UNIT 7
60 AMP DISCONNECTING MEANS HARD WIRED
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
NO GROUNDING ELECTRODE SYSTEM
JUNCTION BOX HAS A BROKEN WOOD POST
THERE ARE EXPOSED CONDUCTORS
UNAPPROVED WIRING METHODS
IMPROPER SPLICED CONNECTIONS






UNIT8
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
NO DEAD FRONT, NO GROUNDING ELECTRODE SYSTEM
METER NIPPLE BROKEN
THE SUPPORT SYSTEM HAS A BROKEN WOOD POST.
ALL ELECTRICAL EQUIPMENT IS UNSTABLE AND NOT PROPERLY SUPPORTED.
MISSING COVER ON THE POWER SUPPLY RECEPTACLE ENCLOSURE.


UNIT 9
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
NO GROUNDING ELECTRODE SYSTEM

UNIT 10
THIS IS THE FIRE DAMAGED UNIT.
THE 200 AMP SERVICE AND THE UNIT'S DISCONNECTING MEANS HAVE BURNT AND ARE NO LONGER SERVICEABLE AND SUITABLE FOR USE.
THIS FIRE DAMAGED EQUIPMENT MUST BE REMOVED.

UNIT 11
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
NO GROUNDING ELECTRODE SYSTEM, UNUSED OPENINGS
THE POWER SUPPLY CORD HAS EXPOSED CONDUCTORS BETWEEN THE CORD AND THE CORD CAP.

UNIT 12
50 AMP DISCONNECTING MEANS
THE POWER SUPPLY CORD HAS EXPOSED CONDUCTORS BETWEEN THE CORD AND THE CORD CAP
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
NO GROUNDING ELECTRODE SYSTEM
UNSECURED POWER SUPPLY RECEPTACLE






UNIT 13
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING OF DISCONNECTING MEANS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE.

UNIT 14
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE
THE POWER SUPPLY CORD IS RATED AT 30 AMPS.
PALLET FENCE IS OBSTRUCTING THE WORKING CLEARING
THE POWER SUPPLY CORD HAS EXPOSED CONDUCTORS BETWEEN THE CORD AND THE CORD CAP

UNIT 15
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
NO DEAD FRONT
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE

UNIT 16
UNABLE TO DETERMINE AMPACITY
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
DISCONNECTING MEANS HAS MISSING FUSE HOLDER
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE










UNIT 17
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
THE POWER SUPPLY CORD HAS EXPOSED CONDUCTORS BETWEEN THE CORD AND THE CORD CAP
50 AMP RECEPTACLE IS CRACKED
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE

UNIT 18
THE DISCONNECTING MEANS IS A PANEL BOARD WITH
DUAL POLE 30 AMP BREAKER AND (3) 20 AMP BREAKERS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
NO DEAD FRONT
NEUTRALS AND GROUNDS ARE NOT SEPARATED
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE

UNIT 19
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE

UNIT 20
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
50 AMP RECEPTACLE IS CRACKED
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE







UNIT 21
30 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
UNSECURED POWER SUPPLY RECEPTACLE
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE

UNIT 22
30 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
UNSECURED POWER SUPPLY RECEPTACLE
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE
POWER SUPPLY RECEPTACLE POST IS BROKEN.

UNIT 23
30 AMP DISCONNECTING MEANS
UNUSED OPENINGS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE
THE GROUNDING ELECTRODE CONDUCTOR HAS MULTIPLE TERMINATIONS
AT THE ACORN CLAMP

UNIT 24
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE
THE GROUNDING ELECTRODE CONDUCTOR HAS MULTIPLE TERMINATIONS
AT THE ACORN CLAMP







UNIT 25
50 AMP DISCONNECTING MEANS
UNUSED OPENINGS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE
THE GROUNDING ELECTRODE CONDUCTOR HAS MULTIPLE TERMINATIONS
AT THE ACORN CLAMP

UNIT 26
80 AMP DISCONNECTING MEANS HARDWIRED
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
NEUTRAL NOT CONNECTED
UNAPPROVED WIRING METHODS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE

UNIT 27
50 AMP DISCONNECTING MEANS
UNUSED OPENINGS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE
NEUTRALS AND GROUNDS ARE NOT SEPARATED
MULTIPLE WIRE TERMINATIONS IN THE SAME TERMINAL LUG
UNAPPROVED WIRING METHODS ON AN ADDITIONAL CIRCUIT WHICH IS MADE UP OF AN EXTENSION CORD RUNNING INSIDE PEX TUBING

UNIT 28
40 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE





UNIT 29
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE
THE GROUNDING ELECTRODE CONDUCTOR HAS MULTIPLE TERMINATIONS
AT THE ACORN CLAMP

UNIT 30
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE
THE GROUNDING ELECTRODE CONDUCTOR HAS MULTIPLE TERMINATIONS
AT THE ACORN CLAMP

LAUNDRY ROOM
UNABLE TO INSPECT
NO ACCESS TO THE EXTERIOR PANEL IT IS BEING OBSTRUCTED BY THE COOLER'S WOOD FRAMED STAND AND THE MAIN SUPPORT SYSTEM TO THE MAIN SERVICE.

UNIT 31
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE

UNIT 32
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE





UNIT 33
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
THE RECEPTACLE SUPPORT POST IS BROKEN
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE

UNIT 34
50 AMP DISCONNECTING MEANS HARDWIRED
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE

UNIT 35
30 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE

UNIT 36
30 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE

UNIT 37
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE






UNIT 38
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE

UNIT 39
60 AMP DISCONNECTING MEANS
RECEPTACLE IS RATED AT 50 AMPS, THE OVER CURRENT PROTECTION IS OVER SIZED FOR ALL DOWN STREAM DEVICES AND USE.
UNUSED OPENINGS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE
NEUTRALS AND GROUNDS ARE NOT SEPARATED


UNIT 40
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE

UNIT 41
65 AMP DISCONNECTING MEANS
UNUSED OPENINGS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
MISSING POWER SUPPLY RECEPTACLE INSIDE THE ENCLOSURE
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE








UNIT 42
30 AMP SINGLE POLE BREAKER IS THE DISCONNECTING MEANS.
THERE ALSO IS (2) 20 AMP CIRCUIT BREAKERS IN THE PANEL
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE
THERE IS EXPOSED UNPROTECTED UF CABLE COMING FROM THE EARTH
THE POWER SUPPLY RECEPTACLE ENCLOSURE IS IN LOT 42 UNABLE TO INSPECT.

UNIT 43
UNABLE TO INSPECT NO ACCESS

UNIT 44
UNABLE TO DETERMINE AMPACITY
THE DISCONNECT HAS MISSING INTERNAL COMPONENTS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
NO DEAD FRONT
USED OPENINGS
NO GROUNDING ELECTRODE SYSTEM

UNIT 45
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE
UNAPPROVED WIRING METHODS
NEUTRALS AND GROUNDS ARE NOT SEPARATED

UNIT 46
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
NO GROUNDING ELECTRODE SYSTEM
EXPOSED UNPROTECTED FEEDERS COMING FROM THE EARTH







UNIT 47
30 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
NO GROUNDING ELECTRODE SYSTEM
EXPOSED CONDUCTORS
THE METER IS NOT PROPERLY SECURED

UNIT 48
UNABLE TO INSPECT NO ACCESS

UNIT 49
UNABLE TO INSPECT NO ACCESS

UNIT 50
30 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
WORK CLEARANCE, EQUIPMENT IS UNDER A COOLER STAND
NO ACCESS
NON SHEATHED METALLIC CABLE RUNS UNDERGROUND
NO GROUNDING ELECTRODE SYSTEM
THE SUPPORT SYSTEM HAS A BROKEN WOOD POST.
ALL ELECTRICAL EQUIPMENT IS UNSTABLE AND NOT PROPERLY SUPPORTED

UNIT 51
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
MISSING DEAD FRONT
UNUSED OPENINGS
EXPOSED CONDUCTORS
WORK CLEARANCE IS BEING OBSTRUCTED BY A WATER PIPE AND A GAS METER.
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE
LOOSE WOOD SUPPORT POST








THERE ARE 250 AMP FUSES IN THE DISCONNECT AT THIS LOCATION
VERIFY THE EQUIPMENT AND ITS USE.
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE
LOOSE WOOD SUPPORT POST

UNIT 52
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
UNUSED OPENINGS
WORK CLEARANCE IS BEING OBSTRUCTED BY COOLER STAND
NO GROUNDING ELECTRODE SYSTEM

UNIT 53
50 AMP DISCONNECTING MEANS HARDWIRED
NO DEAD FRONT ON RECEPTACLE ENCLOSURE
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
NO GROUNDING ELECTRODE SYSTEM

UNIT 54
UNABLE TO DETERMINE AMPACITY OF FUSES UNREADABLE
50 AMP POWER SUPPLY CORD IS HARDWIRED TO THE DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
WORK CLEARANCE IS BEING OBSTRUCTED BY COOLER STAND
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE
NEUTRAL IS NOT CONNECTED
WATER TYPE PVC IS BEING USED AS CONDUIT










UNIT 55
30 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
NO GROUNDING ELECTRODE SYSTEM
CONDUIT NOT PROPERLY SECURED
50 AMP POWER SUPPLY RECEPTACLE HAS EXPOSED CONDUCTORS
ALL ELECTRICAL EQUIPMENT ARE UNSTABLE AND NOT PROPERLY SUPPORTED TO WOOD STRUCTURE.

UNIT 56
60 AMP DISCONNECTING MEANS HARDWIRED
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
TO A 125 AMP PANEL BOARD WHICH IS ATTACHED TO THE MOBILE HOME.
WORK CLEARANCE THE WOOD POST, METER AND DISCONNECT ARE OBSTRUCTING THE PANEL BOARD
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE

UNIT 57
UNABLE TO DETERMINE AMPACITY MISSING FUSE HOLDER
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
THE POWER SUPPLY CORD IS HARDWIRED
MISSING ALL ELECTRICAL INTERNAL COMPONENTS OF THE DISCONNECT MEANS
MISSING METER
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE
EXPOSED CONDUCTORS
THE SUPPORT SYSTEM HAS A BROKEN WOOD POST.
ALL ELECTRICAL EQUIPMENT IS UNSTABLE AND NOT PROPERLY SUPPORTED









UNIT 58
60 AMP DISCONNECTING MEANS
THE POWER SUPPLY CORD IS HARDWIRED
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
NO GROUNDING ELECTRODE SYSTEM

UNIT 59
30 AMP DISCONNECTING MEANS HARDWIRED
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
NO GROUNDING ELECTRODE SYSTEM
WORK CLEARANCE IS BEING OBSTRUCTED BY THE MOBILE HOME
EXPOSED UNPROTECTED FEEDERS COMING FROM THE EARTH
IMPROPER SLICE CONNECTIONS ON THE FEEDERS

UNIT 60
60 AMP DISCONNECTING MEANS
THE OVER CURRENT PROTECTION IS OVER SIZED FOR ALL DOWN STREAM DEVICES AND USE.
50 AMP POWER SUPPLY CORD IS HARDWIRED
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
UNUSED OPENINGS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE

UNIT 61
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
NO GROUNDING ELECTRODE SYSTEM
NEUTRALS AND GROUNDS ARE NOT SEPARATED
WORK CLEARANCE IS BEING OBSTRUCTED BY THE CHAIN LINK FENCE
THE SUPPORT SYSTEM HAS IS DILAPIDATED AND NOT SECURE.
ALL ELECTRICAL EQUIPMENT IS UNSTABLE AND NOT PROPERLY SUPPORTED








UNIT 62
UNABLE TO DETERMINE AMPACITY OF THE DISCONNECT MEANS DUE TO WORK CLEARANCE IS OBSTRUCTED BY A 4X4 POST
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
NO GROUNDING ELECTRODE SYSTEM
EXPOSED CONDUCTORS
THE SUPPORT SYSTEM HAS IS DILAPIDATED AND NOT SECURE.
ALL ELECTRICAL EQUIPMENT IS UNSTABLE AND NOT PROPERLY SUPPORTED

UNIT 63
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE
THE SUPPORT SYSTEM HAS IS DILAPIDATED AND NOT SECURE.
ALL ELECTRICAL EQUIPMENT ARE UNSTABLE AND NOT PROPERLY SUPPORTED

UNIT 64
60 AMP DISCONNECTING MEANS
POWER SUPPLY CORD IS RATED AT 50 AMPS
THE OVER CURRENT PROTECTION IS OVER SIZED FOR ALL DOWN STREAM DEVICES AND USE
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
UNUSED OPENINGS
NO GROUNDING ELECTRODE SYSTEM
EXPOSED CONDUCTORS
WORK CLEARANCE IS OBSTRUCTED BY A WATER LINE

UNIT 65
UNABLE TO DETERMINE AMPACITY OF THE DISCONNECT MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
NO GROUNDING ELECTRODE SYSTEM
RECEPTACLE ENCLOSURE IS NOT PROPERLY SECURED
WORK CLEARANCE IS OBSTRUCTED BY THE GAS METER





UNIT 66
60 AMP DISCONNECTING MEANS
POWER SUPPLY CORD IS RATED AT 30 AMPS
RECEPTACLE IS RATED AT 50 AMPS
THE OVER CURRENT PROTECTION IS OVER SIZED FOR ALL DOWN STREAM DEVICES AND USE
NEUTRALS AND GROUNDS ARE NOT SEPARATED
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE
THE SUPPORT SYSTEM HAS IS DILAPIDATED AND NOT SECURE.
ALL ELECTRICAL EQUIPMENT IS UNSTABLE AND NOT PROPERLY SUPPORTED

UNIT 67
THERE (2) 200 AMPS DISCONNECTS AND A FUSE TYPE OF DISCONNECTING MEANS WHICH I AM UNABLE TO DETERMINE THE AMPACITY OF THE DISCONNECT MEANS DUE TO UNREADABLE FUSES.
EXPOSED UNPROTECTED FEEDERS COMING FROM THE EARTH
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE
UNAPPROVED WIRING METHODS
VERIFY ALL OF THE EQUIPMENT AND ITS USE.

UNIT 68
60 AMP DISCONNECTING MEANS
THE OVER CURRENT PROTECTION IS OVER SIZED FOR ALL DOWN STREAM DEVICES AND USE
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
NO GROUNDING ELECTRODE SYSTEM
UNUSED OPENINGS
EXPOSED CONDUCTORS
THE POWER SUPPLY CORD HAS EXPOSED CONDUCTORS







UNIT 69
60 AMP DISCONNECTING MEANS
THE OVER CURRENT PROTECTION IS OVER SIZED FOR ALL DOWN STREAM DEVICES AND USE
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
WORK CLEARANCE IS BEING OBSTRUCTED BY A WOOD POST
NO GROUNDING ELECTRODE SYSTEM
THE SUPPORT SYSTEM HAS IS DILAPIDATED AND NOT SECURE.
ALL ELECTRICAL EQUIPMENT IS UNSTABLE AND NOT PROPERLY SUPPORTED

UNIT 70
50 AMP DISCONNECTING MEANS
NEUTRALS AND GROUNDS ARE NOT SEPARATED
THERE ALSO ANOTHER 30 AMP FUSE PANEL
VERIFY ALL EQUIPMENT AND ITS USE
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE
MULTIPLE WIRE TERMINATIONS IN THE SAME TERMINAL LUG
THE SUPPORT SYSTEM HAS IS DILAPIDATED AND NOT SECURE.
ALL ELECTRICAL EQUIPMENT IS UNSTABLE AND NOT PROPERLY SUPPORTED

UNIT 71
UNABLE TO DETERMINE AMPACITY OF THE DISCONNECT MEANS DUE TO
MISSING INTERNAL COMPONENTS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
NO POWER SUPPLY RECEPTACLE EQUIPMENT
NO GROUNDING ELECTRODE SYSTEM

UNIT 72
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
POWER SUPPLY CORD IS HARDWIRED
NO GROUNDING ELECTRODE SYSTEM





UNIT 73
60 AMP DISCONNECTING MEANS HARDWIRED
THE OVER CURRENT PROTECTION IS OVER SIZED FOR ALL DOWN STREAM DEVICES AND USE.
POWER SUPPLY CORD IS RATED AT 50 AMPS
NO GROUNDING SYSTEM
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
RECEPTACLE ENCLOSURE IS NOT PROPERLY SECURED
THE SUPPORT SYSTEM HAS IS DILAPIDATED AND NOT SECURE.
ALL ELECTRICAL EQUIPMENT IS UNSTABLE AND NOT PROPERLY SUPPORTED

UNIT 74
50 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
NO GROUNDING ELECTRODE SYSTEM
UNAPPROVED WIRING METHODS
MULTIPLE WIRE TERMINATIONS IN THE SAME TERMINAL LUG
NO GROUNDING ELECTRODE SYSTEM
EXPOSED UNPROTECTED FEEDERS
THE SUPPORT SYSTEM HAS IS DILAPIDATED AND NOT SECURE.
ALL ELECTRICAL EQUIPMENT IS UNSTABLE AND NOT PROPERLY SUPPORTED

UNIT 75
UNABLE TO DETERMINE AMPACITY OF THE DISCONNECT MEANS
NO GROUNDING ELECTRODE SYSTEM
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING OF DISCONNECTING MEANS

UNIT 76 IS LOCATED SECOND ROW FROM THE NORTH SIDE OF THE PARK.
30 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
NEUTRALS AND GROUNDS ARE NOT SEPARATED
NO DEAD FRONT
EXPOSED CONDUCTORS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE
THE POWER SUPPLY RECEPTACLE ENCLOSURE AND THE CONDUIT HAS BEEN DESTROYED


UNIT 80
200 AMP DISCONNECTING MEANS
THERE IS NO CIRCUIT DIRECTORY, IDENTIFICATION OR PROPER LABELING ON DISCONNECTING MEANS
VERIFY THAT THE GROUNDING ELECTRODE SYSTEM HAS 25 OHMS OR LESS TO GROUND. CORRECTION: SUPPLY A SUPPLEMENTAL GROUNDING ELECTRODE.