Case: T14DV07679
Case Details
Entered Date:
09/19/2014
Applicant:
SHARON E CHADWICK & DOUGLAS P CHADWICK
Description:
NO ELECTRICITY SINCE 22ND OF LAST MONTH. Has only 1 working electrical outlet in unit. Owner advised by Section 8 Inspector to have electrical wired correctly by a licensed electrician and has not done so.
Outstanding Inspections
Case Number: T14DV07679
Case Status: COMPLIAN
Case Description: RES: MINIMUM HOUSING
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/29/2014 | NPO(EL)-MAIN/PANEL/SUB/DISCONT | PUMPHREY | Item closed | |
10/29/2014 | NPO(EL)-WIRING/SWITCH/OUTLT/FX | PUMPHREY | Item closed |
Completed Inspections
Case Status: COMPLIAN
Case Number: T14DV07679
Case Description: RES: MINIMUM HOUSING
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/23/2014 | INSP - INITIAL CODE ENFORCMENT | PUMPHREY | Approved | Met owner, tenant, and repair person on site for Unit 704: Laundry closet had 30 amp subpanel connecting a dryer 240 outlet and extra 15/20 amp outlet which then threaded through wall to main panel on east side connecting to a 20 amp breaker which is in turn double lugged to a another separate circuit. This outlet lacks coverplate and appears to have been installed upside down; the laundry closet also has a newly added 15/20 amp circuit feed via same wall from main panel connecting to an non-gfci outlet in kitchen; the conduit is not rated for electrical and is connected to another double lugged 30 amp breaker in panel. Conductors in laundry room have not been installed to code and lack either correct conduit or wire support. 3 breakers are double lugged in main panel; breakers are of different manufacture; dead front is missing; entry into wall via knockout lacks gasket or required wire protection. No permit for added circuits for all three outlets terminating or passing through laundry room. Main panel for non-energized Unit 702 also has double lugged breakers, breakes of different manufacture, a dilapidated 30 amp breaker, and lack of dead front. Repairs will need to be made to bring electrical up to current adopted code under permit. |
10/09/2014 | INSP - FOLLOW UP CODE ENFORCE | PUMPHREY | Approved | Site inspection: partial compliance; double lugging of circuits removed; panel is still missing dead front; unable to verify if circuit removed from laundry room and cover replaced for 220 outlet. |
Outstanding Case Activity Conditions
Date | Name | Approved |
09/24/2014 | T.C. Ch. 16, Sec. 16-11(c) ELECTRICAL SYSTEM. (1) All dwellings and dwelling units shall be provided with electrical service. Electrical facilities connected to or in any building or structure are to be maintained hazard-free and in a state of good repair. The electrical system shall be free from such hazards as bare wiring; overloaded circuits or services; equipment not properly grounded; over-fused circuits; misuse of wiring, including the use of extension cords in lieu of permanent wiring; non-approved wiring; and wiring exposed to moisture or extreme heat. Broken, loose, frayed, inoperable, defective or missing portions of the electrical service, lines, switches, outlets, fixtures and fixture coverings shall be repaired or replaced. (2) All electrical equipment, wiring and appliances shall be installed and maintained in a safe manner and in accordance with all applicable laws. | Not Approved |
Completed Activity Special Conditions
Case Description - RES: MINIMUM HOUSING
Case Number - T14DV07679
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 4
Date | Name |
09/23/2014 | CONTACTED BY PHONE |
09/24/2014 | CONTACTED IN PERSON |
09/24/2014 | NOTICE OF VIOLATION ISSUED |
02/17/2015 | VIOLATION CLOSED |