Case: T14DV02533
Case Details
Entered Date:
04/21/2014
Applicant:
JOSE A QUIROZ
Description:
ELECTRICITY FLICKERING AND OVER CONSUMING (TEP VERIFIED METER/BOX ISSUE), PLUMBING LEAKING EXTERIOR AND SHOWER HEAD CONSTANTLY DRIPPING.
Case Violations
Case Number: T14DV02533
Case Status: COMPLIAN
Case Description: RES: MINIMUM HOUSING
Total Violations: 4
| Violation Date | Code Statue |
|---|---|
| 05/22/2014 | T.C. Ch. 16, Sec. 16-11(a)(3) Every existing dwelling unit shall be provided with smoke detectors in good operating condition as required by the Tucson Fire Code of the City of Tucson. |
| 05/22/2014 | T.C. Ch. 16, Sec. 16-11(c) ELECTRICAL SYSTEM. (1) All dwellings and dwelling units shall be provided with electrical service. Electrical facilities connected to or in any building or structure are to be maintained hazard-free and in a state of good repair. The electrical system shall be free from such hazards as bare wiring; overloaded circuits or services; equipment not properly grounded; over-fused circuits; misuse of wiring, including the use of extension cords in lieu of permanent wiring; non-approved wiring; and wiring exposed to moisture or extreme heat. Broken, loose, frayed, inoperable, defective or missing portions of the electrical service, lines, switches, outlets, fixtures and fixture coverings shall be repaired or replaced. (2) All electrical equipment, wiring and appliances shall be installed and maintained in a safe manner and in accordance with all applicable laws. |
| 05/22/2014 | T.C. Ch. 16, Sec. 16-12(a) EXTERIOR SURFACES. (1) Weather protection. All weather-exposed exterior surfaces of every building, including windows and doors, shall provide weather protection. Every building shall be weather protected to provide shelter for the occupants against the elements and to exclude moisture and dampness. |
| 05/22/2014 | T.C. Ch. 16, Sec. 16-11(e) PLUMBING SYSTEMS. (3) All plumbing systems are to be maintained safe and hazard free and in a state of good repair. Every dwelling or dwelling unit shall have an adequate potable water supply. Every plumbing fixture, water and waste-pipe, and gas connection shall be properly installed in accordance with all applicable laws and maintained in good and sanitary working condition so as to prevent structural deterioration or health hazards, and are to be free from leaks and obstructions. |
Outstanding Inspections
Case Number: T14DV02533
Case Status: COMPLIAN
Case Description: RES: MINIMUM HOUSING
Total Outstanding Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/21/2014 | NPO(EL)-MAIN/PANEL/SUB/DISCONT | BARRON | Item initialized | |
| 04/21/2014 | NPO(EL)-WIRING/SWITCH/OUTLT/FX | BARRON | Item initialized | |
| 04/21/2014 | NPO(PL)-PLUMBING SYSTEM & FX | BARRON | Item initialized |
Completed Inspections
Case Status: COMPLIAN
Case Number: T14DV02533
Case Description: RES: MINIMUM HOUSING
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/01/2014 | INSP - FOLLOW UP CODE ENFORCE | VIDAL | Approved | The owner called and met at the site with an electrician. Did show where the issues of concern were on the electrical flickering. The areas were in the bedroom on the west side and the bathroom. The electrician did check the service panel for the unit in the bedrrom and found 5-loose neutrals. They were tightened and with the other wires check for the proper contacts. Did check the outlets in the bedroom near the living room and found 2-outlets where one has burning where connected to the outlet where loose and the other outlet has loose wiring and not the electrical continue to the other outlets. The outlets were changed to new ones and once they were installed all the power was re-stored. While checking the outlets if they were working, found where the outlets have been painted and the grounding portion has been filled with paint or not allowing the tester to enter for the proper connection to test. Did give the outlets that were removed to the owner and the owner will be changing all the outlet. The electrician will make arrangements to come back to complete the changing of the other outlets including the GFCI in the kitchen and the bathroom due to the test button is painted and getting stuck to turn the power back when testing. Has other issues with the doors not sealed for weatherization, the window in the living room not the proper slider for the window leaving the window not sealed. The master bathroom shower is leaking. Will do N.O.V. RV. |
| 05/01/2014 | INSP - INITIAL CODE ENFORCMENT | VIDAL | Approved | Met with the tenant and the main electrical disconnect has been replaced with a permit due to had burning in the panel for both units. The electrical outlets have issues with not working or partially working. While moving the outlets around to check for power, the outlets started to work. Did talk to the inspector that did the inspection and he did not go inside the unit. The outlets that were checked were the bedrooms on the west side. Will call the owner and stop by the house. RV. |
Completed Activity Special Conditions
Case Description - RES: MINIMUM HOUSING
Case Number - T14DV02533
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 2
| Date | Name |
| 05/02/2014 | CONTACTED BY PHONE |
| 02/23/2015 | VIOLATION CLOSED |