Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T14DV00095
Case Details
Entered Date:
01/07/2014
Applicant:
1050 EAST MOSSMAN LLC ATTN JASON KAPLAN
Description:
ELECTRICAL VIOLATIONS
Case Violations
Case Number: T14DV00095
Case Status: REFERRED
Case Description: WORK WITHOUT PERMITS-COMMERCL
Total Violations: 3
| Violation Date | Code Statue |
|---|---|
| 01/09/2014 | T.C. Ch. 16, Sec. 16-4. PERMITS REQUIRED. Unless otherwise exempt pursuant to section 301 of the Administrative Code, as adopted by reference per section 6-1 of this Code, or pursuant to any other ordinance or statute, no building, structure or building service equipment regulated by this chapter or by the technical codes adopted by the city shall be built, erected, constructed, enlarged, altered, repaired, moved, improved, removed, converted or demolished unless a permit first has been obtained from the building official in the manner provided in the administrative and building codes adopted by the city. The purpose of a permit is to ensure that all construction is inspected by qualified City of Tucson personnel as directed by ordinance to verify compliance with city codes. Failure to obtain proper permit with inspections and approvals shall deem the construction to be unsafe. |
| 01/09/2014 | T.C. Ch. 16, Sec. 16-11(c) ELECTRICAL SYSTEM. (1) All dwellings and dwelling units shall be provided with electrical service. Electrical facilities connected to or in any building or structure are to be maintained hazard-free and in a state of good repair. The electrical system shall be free from such hazards as bare wiring; overloaded circuits or services; equipment not properly grounded; over-fused circuits; misuse of wiring, including the use of extension cords in lieu of permanent wiring; non-approved wiring; and wiring exposed to moisture or extreme heat. Broken, loose, frayed, inoperable, defective or missing portions of the electrical service, lines, switches, outlets, fixtures and fixture coverings shall be repaired or replaced. (2) All electrical equipment, wiring and appliances shall be installed and maintained in a safe manner and in accordance with all applicable laws. |
| 01/09/2014 | T.C. Ch. 16, Sec. 16-11(e) PLUMBING SYSTEMS. (3) All plumbing systems are to be maintained safe and hazard free and in a state of good repair. Every dwelling or dwelling unit shall have an adequate potable water supply. Every plumbing fixture, water and waste-pipe, and gas connection shall be properly installed in accordance with all applicable laws and maintained in good and sanitary working condition so as to prevent structural deterioration or health hazards, and are to be free from leaks and obstructions. |
Outstanding Inspections
Case Number: T14DV00095
Case Status: REFERRED
Case Description: WORK WITHOUT PERMITS-COMMERCL
Total Outstanding Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/19/2014 | NPO(EL)-MAIN/PANEL/SUB/DISCONT | VALDEZ | Item closed | |
| 02/19/2014 | NPO(EL)-WIRING/SWITCH/OUTLT/FX | VALDEZ | Item closed | |
| 02/19/2014 | NPO(PL)-PLUMBING SYSTEM & FX | VALDEZ | Item closed |
Completed Inspections
Case Status: REFERRED
Case Number: T14DV00095
Case Description: WORK WITHOUT PERMITS-COMMERCL
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/08/2014 | INSP - INITIAL CODE ENFORCMENT | VALDEZ | Approved | LAUNDRY ROOM'S ELECTRICAL SERVICE EQUIPMENT HAS A 3 INCH RISER THAT HAS DETACHED ITS SELF FROM THE SUPPORT POST. THE RISER IS LEANING AND NOT PROPERLY SECURED. NEW ELECTRICAL WORK HAS BEEN DONE TO THE SERVICE EQUIPMENT WHICH IS NOT LABELED AND LOCATED NORTH OF UNIT NUMBER 30. NEW PVC CONDUIT HAS BEEN INSTALLED. UNIT NUMBER 30 IS A BUILDING AND THE MAIN DISCONNECT IS NOT PROPERLY SECURED TO THE BUILDING. IT APPEARS THAT THE CONDUIT IS SUPPORTING THE SERVICE. THE PEDESTAL LOCATED AT SPACE NUMBER 44 HAS TWO; 50 AMP RECEPTACLES WHICH DO NOT HAVE OVER CURRENT PROTECTION. THE TRAILER OWNER CAN NOT CONNECT THE 50 AMP LIFE LINE. THE PARKS ABS SEWER PIPE HAS A BROKEN FITTING AND HAS A METAL BOX WHICH HAS BEEN PLACE OVER THE BROKEN FIITING. THERE ARE SEWER GAS ESCAPING DUE TO THE BREAK. THE PARKS WATER SUPPLY LINE WHICH IS A PVC PIPE IS EXPOSED AND NOT PROPERLY SECURED. IT IS A TRIP HAZARD AT THIS TIME. |
| 02/19/2014 | INSP - FOLLOW UP CODE ENFORCE | VALDEZ | Approved | CASE IS TO BE REFERRED T14DV00969 |
Completed Activity Special Conditions
Case Description - WORK WITHOUT PERMITS-COMMERCL
Case Number - T14DV00095
Case Status: REFERRED
Total Completed Case Activity Conditions: 5
| Date | Name |
| 01/08/2014 | CONTACTED BY PHONE |
| 01/09/2014 | CONTACTED IN PERSON |
| 01/30/2014 | CONTACTED BY EMAIL |
| 01/30/2014 | NOTICE OF VIOLATION ISSUED |
| 02/19/2014 | VIOLATION CLOSED |