Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case Details

Status:

COMPLIAN

Type:

RES: MINIMUM HOUSING
Address:

Entered Date:

12/12/2013

Applicant:

MC KINLEY FAMILY LIVING TR ATTN: JOHN P & KATHY A MC KINLEY TR

Description:

NO HEAT FOR A MONTH- AIR BLOWS BUT NO HEAT PROPERTY MGR NOTIFIED OVER A MONTH AGO AND NO RESPONSE/ THERMOSTAT/ LIGHT SWITCHES NOT WORKING PROPERLY.

Case Violations

Case Number: T13DV09246
Case Status: COMPLIAN
Case Description: RES: MINIMUM HOUSING
Total Violations: 3
Violation Date Code Statue
12/16/2013 T.C. Ch. 16, Sec. 16-4. PERMITS REQUIRED. Unless otherwise exempt pursuant to section 301 of the Administrative Code, as adopted by reference per section 6-1 of this Code, or pursuant to any other ordinance or statute, no building, structure or building service equipment regulated by this chapter or by the technical codes adopted by the city shall be built, erected, constructed, enlarged, altered, repaired, moved, improved, removed, converted or demolished unless a permit first has been obtained from the building official in the manner provided in the administrative and building codes adopted by the city. The purpose of a permit is to ensure that all construction is inspected by qualified City of Tucson personnel as directed by ordinance to verify compliance with city codes. Failure to obtain proper permit with inspections and approvals shall deem the construction to be unsafe.
12/16/2013 T.C. Ch. 16, Sec. 16-11(a)(3) Every existing dwelling unit shall be provided with smoke detectors in good operating condition as required by the Tucson Fire Code of the City of Tucson.
12/16/2013 T.C. Ch. 16, Sec. 16-11(b) (1) HEATING. Every habitable room within a dwelling unit, guest room, and congregate residence shall be provided with safe heating facilities which are properly installed and maintained in a sound condition and are capable of providing adequate heating, appropriate for the climate, to assure a safe living environment. All heating facilities shall be free from health hazards associated with ventilation, mounting, electrical and gas connections and other defects. Unvented fuel-burning heaters must be of a listed and approved type, and are prohibited as the sole source of heating. Ovens, stoves or ranges, or other cooking appliances cannot be used for the purpose of heating any portion of a dwelling. Listed, portable space heaters may only be used as the sole source of heating on a temporary basis when the permanent heating system is being repaired or replaced.

Outstanding Inspections

Case Number: T13DV09246
Case Status: COMPLIAN
Case Description: RES: MINIMUM HOUSING
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
12/12/2013 NPO(EL)-WIRING/SWITCH/OUTLT/FX RVIDAL Item closed
12/31/2013 NPO(HC)-HEATING & VENTILATION VINDIOLA Follow-up inspection
12/31/2013 NPO - SMOKE ALARMS VINDIOLA Follow-up inspection
12/31/2013 NPO - WORK WITHOUT PERMIT VINDIOLA Follow-up inspection

Completed Inspections

Case Status: COMPLIAN
Case Number: T13DV09246
Case Description: RES: MINIMUM HOUSING
Total Completed Inspections - 2
End Date Description Inspector Results Comments
12/12/2013 INSP - INITIAL CODE ENFORCMENT RVIDAL Approved Rick Saldate gave the case to me to have the property checked for no heat. Arrived and met with the tenant and he showed how the thermostat was loose on the wall. He did push he setting to 90 degrees and the heater was working. I was able to check the temperature and was 110 to 112 degrees at the vents coming out. I did stay for a while to check the unit and found the water heater lacking the drain line for the T.P.R. The water heater is new and has been replaced in 2009. Will need to check for the permit. Lacking smoke detectors on a one bedroom. The unit did get hot and the tenant stated that it's working. I will do N.O.V. RV.
12/31/2013 INSP - FOLLOW UP CODE ENFORCE AVINDIOL Approved 12/31/13 ARRIVED ON SITE MET WITH MANAGER // STATES NEVER REC'D NOTICE PROVIDED HER WITH A COPY // TENANTS MOVED OUT AND HASNT GAIN CONTROL OF UNIT YET BUT WILL TAKE CARE OF SMOKE DETECTORS AND THERMOSTAT BY TUESDAY // AV

Completed Activity Special Conditions

Case Description - RES: MINIMUM HOUSING
Case Number - T13DV09246
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 3
Date Name
12/19/2013 CONTACTED BY MAILING
12/19/2013 NOTICE OF VIOLATION ISSUED
02/19/2014 VIOLATION CLOSED