Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLIAN

Type:

RES: MINIMUM HOUSING

Entered Date:

08/10/2012

Applicant:

JULIE J. CHEN

Description:

Reaching 95 degrees inside of unit; wall unit is undersized and installed incorrectly. Plumbing/shower/kitchen sink draining into ground outside in yard and strong sewage smell. Issues reported to property manager.

Case Violations

Case Number: T12DV06929
Case Status: COMPLIAN
Case Description: RES: MINIMUM HOUSING
Total Violations: 4
Violation Date Code Statue
08/17/2012 T.C. Ch. 16, Sec. 16-4. PERMITS REQUIRED. Unless otherwise exempt pursuant to section 301 of the Administrative Code, as adopted by reference per section 6-1 of this Code, or pursuant to any other ordinance or statute, no building, structure or building service equipment regulated by this chapter or by the technical codes adopted by the city shall be built, erected, constructed, enlarged, altered, repaired, moved, improved, removed, converted or demolished unless a permit first has been obtained from the building official in the manner provided in the administrative and building codes adopted by the city. The purpose of a permit is to ensure that all construction is inspected by qualified City of Tucson personnel as directed by ordinance to verify compliance with city codes. Failure to obtain proper permit with inspections and approvals shall deem the construction to be unsafe.
08/17/2012 T.C. Ch. 16, Sec. 16-11(c) ELECTRICAL SYSTEM. (1) All dwellings and dwelling units shall be provided with electrical service. Electrical facilities connected to or in any building or structure are to be maintained hazard-free and in a state of good repair. The electrical system shall be free from such hazards as bare wiring; overloaded circuits or services; equipment not properly grounded; over-fused circuits; misuse of wiring, including the use of extension cords in lieu of permanent wiring; non-approved wiring; and wiring exposed to moisture or extreme heat. Broken, loose, frayed, inoperable, defective or missing portions of the electrical service, lines, switches, outlets, fixtures and fixture coverings shall be repaired or replaced. (2) All electrical equipment, wiring and appliances shall be installed and maintained in a safe manner and in accordance with all applicable laws.
08/17/2012 T.C. Ch. 16, Sec. 16-11(e) PLUMBING SYSTEMS. (3) All plumbing systems are to be maintained safe and hazard free and in a state of good repair. Every dwelling or dwelling unit shall have an adequate potable water supply. Every plumbing fixture, water and waste-pipe, and gas connection shall be properly installed in accordance with all applicable laws and maintained in good and sanitary working condition so as to prevent structural deterioration or health hazards, and are to be free from leaks and obstructions.
08/17/2012 T.C. Ch. 16, Sec. 16-11(e) PLUMBING SYSTEMS. (4) All plumbing fixtures shall be connected to a public sewer system or to an approved private sewage disposal system, with the connections free from leaks, blockages, or other defects. All plumbing fixtures shall be connected to an approved system of water supply and provided with hot and cold running water necessary for its normal operation.

Outstanding Inspections

Case Number: T12DV06929
Case Status: COMPLIAN
Case Description: RES: MINIMUM HOUSING
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
08/20/2012 NPO(HC)-COOLING MROMERO Item closed
12/10/2012 NPO(EL)-MAIN/PANEL/SUB/DISCONT MROMERO Item closed
12/10/2012 NPO(EL)-WIRING/SWITCH/OUTLT/FX MROMERO Item closed
12/10/2012 NPO(PL)-PLUMBING SYSTEM & FX MROMERO Item closed
12/10/2012 NPO(PL)-WATER HEATERS MROMERO Item closed
12/10/2012 NPO - WORK WITHOUT PERMIT MROMERO Item closed

Completed Inspections

Case Status: COMPLIAN
Case Number: T12DV06929
Case Description: RES: MINIMUM HOUSING
Total Completed Inspections - 2
End Date Description Inspector Results Comments
08/14/2012 INSP - INITIAL CODE ENFORCMENT MROMERO Approved CALLOUT FOR NO AC. TENANT IS HANDICAP IN WHEEL CHAIR. 100 AMP SERVICE WITH HAZARDOUS WIRING TO INCLUDE DOUBLE LUGGING AT 30 AMP FOR DRYER 15 AMP FOR WASHER ALSO DOUBLE LUGGING AT 30 AMP FOR WALL MOUNT AC UNIT NO PERMITS SERVICE PANEL ALSO HAS NO COVER PLATE ILLEGAL USE OF ROMEX HAZARDLY CONNECTED TO PANEL WITHOUT PROPER PERMITS. OUTSIDE OUTLETS ARE NOT GFCI PROTECTED. PLUMBING FROM BATHROOM AND WASHER NOT PERMITTED IN EVIDENT BY MIXING OF APEC AND PVC. HOT WATER HEATER LEAKS AT DRAIN AND TOP OF UNIT. COPPER HAS CALISFIED, PLUMBING FROM HOTWATER HEATER TO WASHER LACKS PERMITS. REPLACEMENT OF HOT WATER HEATER IS REQUIRED WITH PERMITS. INTERIOR APPEARED TO CARPORT COVERTED TO GUEST HOUSE. REASEARCH SHOWS PERMIT FINAL STATUS T07CM03782.
12/10/2012 INSP - FOLLOW UP CODE ENFORCE MROMERO Approved ALL WORK COMPLETED WITH PERMIT IN FINAL STATUS, CLOSE.

Completed Activity Special Conditions

Case Description - RES: MINIMUM HOUSING
Case Number - T12DV06929
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 6
Date Name
08/14/2012 CONTACTED BY PHONE
08/20/2012 CONTACTED BY MAILING
08/20/2012 NOTICE OF VIOLATION ISSUED
12/26/2012 VIOLATION CLOSED
09/28/2012 REINSPECTION FEE - FIRST
08/31/2012 REINSP POSTCARD SENT

Documents

File Name Document Type  
1501 E SENECA #2 001.JPG IMAGES VIEW
1501 E SENECA #2 002.JPG IMAGES VIEW
1501 E SENECA #2 003.JPG IMAGES VIEW
1501 E SENECA #2 004.JPG IMAGES VIEW
1501 E SENECA #2 005.JPG IMAGES VIEW
1501 E SENECA #2 006.JPG IMAGES VIEW
1501 E SENECA #2 007.JPG IMAGES VIEW
1501 E SENECA #2 008.JPG IMAGES VIEW
1501 E SENECA #2 009.JPG IMAGES VIEW
1501 E SENECA #2 010.JPG IMAGES VIEW
1501 E SENECA #2 011.JPG IMAGES VIEW
1501 E SENECA #2 012.JPG IMAGES VIEW
1501 E SENECA #2 013.JPG IMAGES VIEW
1501 E SENECA #2 014.JPG IMAGES VIEW
1501 E SENECA #2 015.JPG IMAGES VIEW
1501 E SENECA #2 016.JPG IMAGES VIEW
1501 E SENECA #2 017.JPG IMAGES VIEW
THUMBS.DB IMAGES VIEW