Case: T12DV06929

Parcel: 123120070

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Case Number - T12DV06929

Inspection Description - INSP - INITIAL CODE ENFORCMENT

Inspection Status - Approved

Date Description Inspector Results Comments
08/14/2012 INSP - INITIAL CODE ENFORCMENT Approved CALLOUT FOR NO AC. TENANT IS HANDICAP IN WHEEL CHAIR.
100 AMP SERVICE WITH HAZARDOUS WIRING TO INCLUDE DOUBLE LUGGING AT 30 AMP FOR DRYER
15 AMP FOR WASHER
ALSO DOUBLE LUGGING AT 30 AMP FOR WALL MOUNT AC UNIT NO PERMITS
SERVICE PANEL ALSO HAS NO COVER PLATE
ILLEGAL USE OF ROMEX HAZARDLY CONNECTED TO PANEL WITHOUT PROPER PERMITS.
OUTSIDE OUTLETS ARE NOT GFCI PROTECTED.

PLUMBING FROM BATHROOM AND WASHER NOT PERMITTED IN EVIDENT BY MIXING OF APEC AND PVC.
HOT WATER HEATER LEAKS AT DRAIN AND TOP OF UNIT. COPPER HAS CALISFIED, PLUMBING FROM HOTWATER HEATER TO WASHER LACKS PERMITS.
REPLACEMENT OF HOT WATER HEATER IS REQUIRED WITH PERMITS.
INTERIOR APPEARED TO CARPORT COVERTED TO GUEST HOUSE. REASEARCH SHOWS PERMIT FINAL STATUS T07CM03782.