Case Details

Status:

COMPLIAN

Type:

MULTIPLE TYPES

Entered Date:

06/04/2012

Applicant:

GOODMAN BEATRICE PRESCOTT UND & GOODMAN LUCY PRESCOTT

Description:

WIRING FOR ELECTRIC, LEAK IN THE BRATHROOMS,

Case Violations

Case Number: T12DV04563
Case Status: COMPLIAN
Case Description: MULTIPLE TYPES
Total Violations: 2
Violation Date Code Statue
06/07/2012 T.C. Ch. 16, Sec. 16-4. PERMITS REQUIRED. Unless otherwise exempt pursuant to section 301 of the Administrative Code, as adopted by reference per section 6-1 of this Code, or pursuant to any other ordinance or statute, no building, structure or building service equipment regulated by this chapter or by the technical codes adopted by the city shall be built, erected, constructed, enlarged, altered, repaired, moved, improved, removed, converted or demolished unless a permit first has been obtained from the building official in the manner provided in the administrative and building codes adopted by the city. The purpose of a permit is to ensure that all construction is inspected by qualified City of Tucson personnel as directed by ordinance to verify compliance with city codes. Failure to obtain proper permit with inspections and approvals shall deem the construction to be unsafe.
06/07/2012 T.C. Ch. 16, Sec. 16-11(c) ELECTRICAL SYSTEM. (1) All dwellings and dwelling units shall be provided with electrical service. Electrical facilities connected to or in any building or structure are to be maintained hazard-free and in a state of good repair. The electrical system shall be free from such hazards as bare wiring; overloaded circuits or services; equipment not properly grounded; over-fused circuits; misuse of wiring, including the use of extension cords in lieu of permanent wiring; non-approved wiring; and wiring exposed to moisture or extreme heat. Broken, loose, frayed, inoperable, defective or missing portions of the electrical service, lines, switches, outlets, fixtures and fixture coverings shall be repaired or replaced. (2) All electrical equipment, wiring and appliances shall be installed and maintained in a safe manner and in accordance with all applicable laws.

Outstanding Inspections

Case Number: T12DV04563
Case Status: COMPLIAN
Case Description: MULTIPLE TYPES
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
08/20/2012 NPO(EL)-WIRING/SWITCH/OUTLT/FX DJOHNSTO Item closed
08/20/2012 NPO(PL)-PLUMBING SYSTEM & FX DJOHNSTO Item closed

Completed Inspections

Case Status: COMPLIAN
Case Number: T12DV04563
Case Description: MULTIPLE TYPES
Total Completed Inspections - 2
End Date Description Inspector Results Comments
06/05/2012 INSP - INITIAL CODE ENFORCMENT DJOHNSTO Approved Calking in the shower in the bathroom is missing and leaking into the wall causing mold. Electrical circuits added without permit. New circuit installed from fusebox for dishwasher without permit. Some double lugging. Wires in upper cabinet above the sink are terminated with wire nuts. Receptacle installed under the sink for dishwasher. Breakers pop when using more than one appliance. Breakers not properly labeled. New 20 amp breaker installed in panel. Send 30 day notice. Schedule follow up inspection.
07/18/2012 INSP - FOLLOW UP CODE ENFORCE DJOHNSTO Approved Permit is issued for electrical T12CM03607. Followup in 30 days.

Completed Activity Special Conditions

Case Description - MULTIPLE TYPES
Case Number - T12DV04563
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 5
Date Name
06/07/2012 CONTACTED IN PERSON
06/08/2012 CONTACTED BY MAILING
06/08/2012 NOTICE OF VIOLATION ISSUED
08/20/2012 VIOLATION CLOSED
06/07/2012 RESEARCH