Case: T11FR01006
Case Details
Entered Date:
05/24/2011
Applicant:
26 PALMS DELAWARE LLC & SIERRA INDUSTRIAL
Description:
Sprinkler Deficiencies
Outstanding Inspections
Case Number: T11FR01006
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - REINSPECTION | None | Not Inspected | ||
| 05/23/2011 | VIOL - FIRE PROTECTION SYSTEMS | CSCHULTZ | Correction Required | 1. Riser # 1 (east) the bottom gauge port is plugged. Shall repair 2. Pressure gauges are outdated - Shall recalibrate or replace gauges. 3. The 6" Kennedy riser control valve will not close. - Shall repair or replace valve. 4. Shall have a 5 year check valve inspection done. 5. Shall have a sprinkler inspection done on properties. |