Case: T11FR01006

Parcel: 13510150R

Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T11FR01006

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
05/23/2011 VIOL - FIRE PROTECTION SYSTEMS Correction Required 1. Riser # 1 (east) the bottom gauge port is plugged. Shall repair
2. Pressure gauges are outdated - Shall recalibrate or replace gauges.
3. The 6" Kennedy riser control valve will not close. - Shall repair or replace valve.
4. Shall have a 5 year check valve inspection done.
5. Shall have a sprinkler inspection done on properties.