Inspection Status: Correction Required
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/23/2011 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 1. Riser # 1 (east) the bottom gauge port is plugged. Shall repair 2. Pressure gauges are outdated - Shall recalibrate or replace gauges. 3. The 6" Kennedy riser control valve will not close. - Shall repair or replace valve. 4. Shall have a 5 year check valve inspection done. 5. Shall have a sprinkler inspection done on properties. |