Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

04/28/2011

Applicant:

NOVITT DAVID C & SANDRA I

Description:

Performance Upholstery 4/28/11 Debbie Derton 792-4444

Outstanding Inspections

Case Number: T11FR00943
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
04/28/2011 VIOL - ADMINISTRATION MPursley Correction Required
04/28/2011 VIOL - PRECAUTION AGAINST FIRE MPursley Correction Required 315.2 Storage in buildings Storage of combustible materials shall be orderly. Storage shall be separated from heaters or heating devices so that ignition cannot occur. ____Keep hot water heater clear. 315.2.1 Ceiling clearance Storage shall be maintained 2 feet or more below the ceiling in non-sprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of a building. _____ Maintain proper ceiling clearance according to code.
04/28/2011 VIOL - EMERGENCY PLAN/PREPARE MPursley Correction Required 407.2 Material Safety Data Sheets. Material Safety Data Sheets (MSDS) for all hazardous materials shall be readily available on the premises. _____Have MSDS' readily available
04/28/2011 VIOL - BUILDING SVCS & SYSTEMS MPursley Correction Required 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used… Electrical blanks shall be placed in all open spaces within any electrical panel or box. _____ Remove modification to breaker box. 605.6 Unapproved conditions Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switch and outlet covers. _____ Place approved cover(s) over the electrical wiring in office and workshop.
04/28/2011 VIOL - FIRE PROTECTION SYSTEMS MPursley Correction Required 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. ______ Service, tag, maintain, and properly hang all portable fire extinguishers according to code
04/28/2011 VIOL - MEANS OF EGRESS MPursley Correction Required 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____ Remove the padlock from exit 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. _____ Remove all obstructions and be sure to always maintain a clear and obstruction free path from your stairs to exit.
04/28/2011 VIOL - FLAMMABLE FINISHES MPursley Correction Required 1503.2.6 Smoking prohibited. Smoking shall be prohibited in flammable vapor areas and hazardous materials storage rooms associated with flammable finish processes. "No Smoking" signs complying with Section 310 shall be conspicuously posted in such areas. 1503.2.7 Welding warning signs. Welding, cutting and similar spark-producing operations shall not be conducted in or adjacent to flammable vapor areas or dipping or coating operations unless precautions have been taken to provide safety. Conspicuous signs with the following warning shall be posted in the vicinity of flammable vapor areas, dipping operations and paint storage rooms: NO WELDING THE USE OF WELDING OR CUTTING EQUIPMENT IN OR NEAR THIS AREA IS DANGEROUS BECAUSE OF FIRE AND EXPLOSION HAZARDS. WELDING AND CUTTING SHALL BE DONE ONLY UNDER THE SUPERVISION OF THE PERSON IN CHARGE. 1504.9 Limited spraying spaces. Limited spraying spaces shall comply with Sections 1504.9.1 through 1504.9.4. 1504.9.1 Job size. The aggregate surface area to be sprayed shall not exceed 9 square feet (0.84 m2). 1504.9.2 Frequency. Spraying operations shall not be of a continuous nature. 1504.9.3 Ventilation. Positive mechanical ventilation providing a minimum of six complete air changes per hour shall be installed. Such system shall meet the requirements of this code for handling flammable vapor areas. Explosion venting is not required. 1504.9.4 Electrical wiring. Electrical wiring within 10 feet (3048 mm) of the floor and 20 feet (6096 mm) horizontally of the limited spraying space shall be designed for Class I, Division 2 locations in accordance with the ICC Electrical Code. _____Comply with limited spraying space requirements for flammable adhesive spraying
04/28/2011 VIOL - HAZARDOUS MATERIALS,GEN MPursley Correction Required 2703.1 Maximum Allowable Quantities: Class IA Flammable liquids: 30gal. can be doubled with proper cabinet and doubled again if sprinklered. 2703.5 Hazard identification signs. Unless otherwise exempted by the fire code official, visible hazard identification signs as specified in NFPA 704 for the specific material contained shall be placed on stationary containers and above-ground tanks and at entrances to locations where hazardous materials are stored, dispensed, used or handled in quantities requiring a permit and at specific entrances and locations designated by the fire code official. _____Place NFPA 704 marking on front and back of store

Completed Inspections

Case Status: FIELD
Case Number: T11FR00943
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/03/2011 INSP - REINSPECTION MPursley Approved All corrections made 8/2/11