Case: T11FR00943

Parcel: 129042800


Addresses:

1934 E 13TH ST


Inspection Status: Correction Required

Inspection History: VIOL - FLAMMABLE FINISHES

Case Number - T11FR00943

Inspection Description - VIOL - FLAMMABLE FINISHES

Inspection Status - Correction Required

Date Description Inspector Results Comments
04/28/2011 VIOL - FLAMMABLE FINISHES Correction Required 1503.2.6 Smoking prohibited.
Smoking shall be prohibited in flammable vapor areas and hazardous materials storage rooms associated with flammable finish processes. "No Smoking" signs complying with Section 310 shall be conspicuously posted in such areas.

1503.2.7 Welding warning signs.
Welding, cutting and similar spark-producing operations shall not be conducted
in or adjacent to flammable vapor areas or dipping or coating operations unless precautions have been taken to provide safety. Conspicuous signs with the following warning shall be posted in the vicinity of flammable vapor areas, dipping operations and paint storage rooms:

NO WELDING
THE USE OF WELDING OR CUTTING
EQUIPMENT IN OR NEAR THIS AREA
IS DANGEROUS BECAUSE OF FIRE
AND EXPLOSION HAZARDS. WELDING
AND CUTTING SHALL BE DONE ONLY
UNDER THE SUPERVISION OF THE
PERSON IN CHARGE.

1504.9 Limited spraying spaces.
Limited spraying spaces shall comply with Sections 1504.9.1 through 1504.9.4.

1504.9.1 Job size.
The aggregate surface area to be sprayed shall not exceed 9 square feet (0.84 m2).

1504.9.2 Frequency.
Spraying operations shall not be of a continuous nature.

1504.9.3 Ventilation.
Positive mechanical ventilation providing a minimum of six complete air changes per hour shall be installed. Such system shall meet the requirements of this code for handling flammable vapor areas. Explosion venting is not required.

1504.9.4 Electrical wiring.
Electrical wiring within 10 feet (3048 mm) of the floor and 20 feet (6096 mm) horizontally of the limited spraying space shall be designed for Class I, Division 2 locations in accordance with the ICC Electrical Code.


_____Comply with limited spraying space requirements for flammable adhesive spraying