Case: T11FR00856
Case Details
Entered Date:
04/19/2011
Applicant:
SAINT JOHN THE EVANGELIST ROMAN
Description:
Private school full inspetion
Outstanding Inspections
Case Number: T11FR00856
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/19/2011 | INSP - FULL | BCORRALE | Continued | Full fire and life safety inspection consducted on 04/19/2011. |
04/19/2011 | VIOL - BUILDING SVCS & SYSTEMS | BCORRALE | Violation | Extension cords are used as permanent wiring in the following locations: - Room 1 - Room 2 (3 cords) - Room 5 - Room 8 - Room 10 Remove cords from use. A power strip with a longer cord would be acceptable, plugged in to a permanent outlet. 2006 IFC 605.5 |
04/19/2011 | VIOL - BUILDING SVCS & SYSTEMS | BCORRALE | Violation | Open junction box with exposed wiring. (cafeteria, south exit, above door.) 2006 IFC 605.6 Repair box with approved cover. |
04/19/2011 | VIOL - FIRE PROTECTION SYSTEMS | BCORRALE | Violation | Fire alarm panel overdue for annual testing. (July 2009). 2006 IFC 901.6 _Ensure annual test is conducted, and a copy is fowarded to TFD. |
04/19/2011 | VIOL - FIRE PROTECTION SYSTEMS | BCORRALE | Violation | Fire extinguisher are overdue for annual tests in the following locations: - Room 6 (October 2008) - Title 1 trailer (May 2002) - Administration office (July 2009) 2006 IFC 901.6 _Ensure annual testing. |