Private school full inspetion

Outstanding Inspections

Case Number: T11FR00856
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
04/19/2011 INSP - FULL BCORRALE Continued Full fire and life safety inspection consducted on 04/19/2011.
04/19/2011 VIOL - BUILDING SVCS & SYSTEMS BCORRALE Violation Extension cords are used as permanent wiring in the following locations: - Room 1 - Room 2 (3 cords) - Room 5 - Room 8 - Room 10 Remove cords from use. A power strip with a longer cord would be acceptable, plugged in to a permanent outlet. 2006 IFC 605.5
04/19/2011 VIOL - BUILDING SVCS & SYSTEMS BCORRALE Violation Open junction box with exposed wiring. (cafeteria, south exit, above door.) 2006 IFC 605.6 Repair box with approved cover.
04/19/2011 VIOL - FIRE PROTECTION SYSTEMS BCORRALE Violation Fire alarm panel overdue for annual testing. (July 2009). 2006 IFC 901.6 _Ensure annual test is conducted, and a copy is fowarded to TFD.
04/19/2011 VIOL - FIRE PROTECTION SYSTEMS BCORRALE Violation Fire extinguisher are overdue for annual tests in the following locations: - Room 6 (October 2008) - Title 1 trailer (May 2002) - Administration office (July 2009) 2006 IFC 901.6 _Ensure annual testing.