Case: T11FR00856

Parcel: 11918036A


Addresses:

600 W AJO WY


Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T11FR00856

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
04/19/2011 VIOL - BUILDING SVCS & SYSTEMS Violation Extension cords are used as permanent wiring in the following locations:

- Room 1
- Room 2 (3 cords)
- Room 5
- Room 8
- Room 10

Remove cords from use. A power strip with a longer cord would be acceptable, plugged in to a permanent outlet. 2006 IFC 605.5
04/19/2011 VIOL - BUILDING SVCS & SYSTEMS Violation Open junction box with exposed wiring. (cafeteria, south exit, above door.) 2006 IFC 605.6

Repair box with approved cover.