Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T11FR00468
Case Details
Entered Date:
02/18/2011
Applicant:
PARK VIEW PLAZA INC
Description:
Bamboo Terrace fire inspection.
Outstanding Inspections
Case Number: T11FR00468
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/18/2011 | VIOL - FIRE SERVICE FEATURES | JLOYA | Violation | 505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. Address numbers shall be in accordance with Pima County address display requirements. Building < 50 feet from the curb require 12" numbers displayed on the building. Buildings > 50 feet from the curb require 15" numbers displayed on the building. Tenant space numbers shall be 3" Address range may be displayed in 12" numbers on the building. |
02/18/2011 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | 904.11.6.3 - Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. ___ Main Hood filters are very dirty with grease, time between hood cleanings need to be shortened. |
02/18/2011 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate… The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. _____ Repair or replace emergency lighting |
02/18/2011 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1008.1.8.1 Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate __ Remove extra latch at emergency exit. |
02/18/2011 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background |
02/18/2011 | VIOL - MEANS OF EGRESS | JLOYA | Violation | 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs |
Completed Inspections
Case Status: COMPLETE
Case Number: T11FR00468
Case Description: INSPECTION
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/18/2011 | INSP - FULL | JLOYA | Approved | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________ |
03/10/2011 | INSP - REINSPECTION | JLOYA | Approved | Violations abated. |