Case: T11FR00468

Parcel: 119215900


Addresses:

1754 W AJO WY


Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T11FR00468

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Violation

Date Description Inspector Results Comments
02/18/2011 VIOL - MEANS OF EGRESS Violation 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate…
The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator.

_____ Repair or replace emergency lighting
02/18/2011 VIOL - MEANS OF EGRESS Violation 1008.1.8.1 Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate
__ Remove extra latch at emergency exit.
02/18/2011 VIOL - MEANS OF EGRESS Violation 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background
02/18/2011 VIOL - MEANS OF EGRESS Violation 1011.2 - Illumination. Exit signs shall be internally or externally illuminated.

_____ Repair/replace exit signs