Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

02/01/2011

Applicant:

TMC HOLDINGS INC

Description:

FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T11FR00320
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 13
End Date Description Inspector Results Comments
02/01/2011 INSP - FULL RSPANGLE Violation 1.) TFC 315.2.1 STORAGE MUST BE MAINTAINED 18" BELOW SPRINKLER HEAD DEFLECTOR IN STORAGE CLOSET BY ROOM# 446.
02/01/2011 INSP - FULL RSPANGLE Violation 10.) TFC 1011.4 EXIT SIGN IS NOT ILLUMINATED FOR EXIT DOOR FROM NICU BY ROOM # 145.
02/01/2011 INSP - FULL RSPANGLE Violation 11.) TFC 1011.1 AN APPROVED EXIT SIGN IS REQUIRED IN CORRIDOR OF NURSES OFFICES/NEWORNS TO INDICATE LOCATION OF EXIT DOOR.
02/01/2011 INSP - FULL RSPANGLE Violation 12.) TFC 1011.4 EXIT SIGN IS NOT ILLUMINATED OVER SAME EXIT DOOR NOTED IN ITEM #11.
02/01/2011 INSP - FULL RSPANGLE Violation 13.) TFC 1011.4 EXIT SIGN IS NOT ILLUMINATED ABOVE SOUTH EXIT DOOR OF WELL BABY NURSERY.
02/01/2011 INSP - FULL RSPANGLE Violation 2.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON OUTSIDE OF ROOM # 446
02/01/2011 INSP - FULL RSPANGLE Violation 3.) TFC 901.6 IN UNIT 470 IN SOUTH I/S CLOSET REPLACE BROKEN CEILING TILE, REPLACE MISSING ESCUTCHEON, SEAL WALL PENETRATIONS & SEAL AROUND CABLES IN CONDUIT.
02/01/2011 INSP - FULL RSPANGLE Violation 4.) TFC 703.1.1 SEAL WALL PENETRATION NEAR THE FLOOR IN 490'S EAST WALL OF CORRIDOR BY ROOM # 496.
02/01/2011 INSP - FULL RSPANGLE Violation 5.) TFC 703.1.1 REPAIR WALL PENETRATION BEHIND DOOR IN STORAGE ROOM SOUTH OF ROOM # 186.
02/01/2011 INSP - FULL RSPANGLE Violation 6.) TFC 1011.4 TWO EXIT SIGNS FOR EAST EXIT DOORS FROM L&D PATIENT ROOMS ARE NOT ILLUMINATED.
02/01/2011 INSP - FULL RSPANGLE Violation 7.) TFC 703.1.1 SEAL CEILING PENETRATIONS IN I/S CLOSET IN EAST-WEST HALLWAY OF L&D.
02/01/2011 INSP - FULL RSPANGLE Violation 8.) TFC 315.2.3 REMOVE MOBILE POP-UP CONTAINMENT UNIT FROM ELECTRICAL EQUIPMENT ROOM IN L&D.
02/01/2011 INSP - FULL RSPANGLE Violation 9.) TFC 1011.4 EXIT SIGN IS NOT ILLUMINATED FOR WEST EXIT DOOR BY NICU NURSES STATION.