Inspection Status: Violation
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/01/2011 |
INSP - FULL |
|
Violation |
1.) TFC 315.2.1 STORAGE MUST BE MAINTAINED 18" BELOW SPRINKLER HEAD DEFLECTOR IN STORAGE CLOSET BY ROOM# 446. |
| 02/01/2011 |
INSP - FULL |
|
Violation |
2.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON OUTSIDE OF ROOM # 446 |
| 02/01/2011 |
INSP - FULL |
|
Violation |
3.) TFC 901.6 IN UNIT 470 IN SOUTH I/S CLOSET REPLACE BROKEN CEILING TILE, REPLACE MISSING ESCUTCHEON, SEAL WALL PENETRATIONS & SEAL AROUND CABLES IN CONDUIT. |
| 02/01/2011 |
INSP - FULL |
|
Violation |
4.) TFC 703.1.1 SEAL WALL PENETRATION NEAR THE FLOOR IN 490'S EAST WALL OF CORRIDOR BY ROOM # 496. |
| 02/01/2011 |
INSP - FULL |
|
Violation |
5.) TFC 703.1.1 REPAIR WALL PENETRATION BEHIND DOOR IN STORAGE ROOM SOUTH OF ROOM # 186. |
| 02/01/2011 |
INSP - FULL |
|
Violation |
6.) TFC 1011.4 TWO EXIT SIGNS FOR EAST EXIT DOORS FROM L&D PATIENT ROOMS ARE NOT ILLUMINATED. |
| 02/01/2011 |
INSP - FULL |
|
Violation |
7.) TFC 703.1.1 SEAL CEILING PENETRATIONS IN I/S CLOSET IN EAST-WEST HALLWAY OF L&D. |
| 02/01/2011 |
INSP - FULL |
|
Violation |
8.) TFC 315.2.3 REMOVE MOBILE POP-UP CONTAINMENT UNIT FROM ELECTRICAL EQUIPMENT ROOM IN L&D. |
| 02/01/2011 |
INSP - FULL |
|
Violation |
9.) TFC 1011.4 EXIT SIGN IS NOT ILLUMINATED FOR WEST EXIT DOOR BY NICU NURSES STATION. |
| 02/01/2011 |
INSP - FULL |
|
Violation |
10.) TFC 1011.4 EXIT SIGN IS NOT ILLUMINATED FOR EXIT DOOR FROM NICU BY ROOM # 145. |
| 02/01/2011 |
INSP - FULL |
|
Violation |
11.) TFC 1011.1 AN APPROVED EXIT SIGN IS REQUIRED IN CORRIDOR OF NURSES OFFICES/NEWORNS TO INDICATE LOCATION OF EXIT DOOR. |
| 02/01/2011 |
INSP - FULL |
|
Violation |
12.) TFC 1011.4 EXIT SIGN IS NOT ILLUMINATED OVER SAME EXIT DOOR NOTED IN ITEM #11. |
| 02/01/2011 |
INSP - FULL |
|
Violation |
13.) TFC 1011.4 EXIT SIGN IS NOT ILLUMINATED ABOVE SOUTH EXIT DOOR OF WELL BABY NURSERY. |