Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T11FR00249
Case Details
Entered Date:
01/26/2011
Applicant:
GRABB ROBERT M &
Description:
Generated by T10BU01929
Outstanding Inspections
Case Number: T11FR00249
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/25/2011 | VIOL - TENTS, CANOPIES & OTHER | dgreenl1 | Violation | Because canopy has ben converted to a tent, you are required additional safeguards: 1) emergency egress lighting that is activited by the loss of power to primary lighting 2) continuously illuminated EXIT signs over all 3 exits Additionally: the following deficiencies that were not present at the time your permit was approved shall be corrected: 3) Support poles shall be anchored in such a way as to fully support the tent 4) All panels in a tent shall be fire rated - provide proof of fire rating for "billboard" panels or replace with approved ones. 5) Use of liquid fueled kerosene heater is prohibited in tent 6) Generator shall be located at least 10' from tent and shall have adequate clearance from all combustables |
Completed Inspections
Case Status: COMPLETE
Case Number: T11FR00249
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/11/2011 | INSP - REINSPECTION | dgreenl1 | Approved | Tent has been removed |