Outstanding Inspections

Case Number: T11FR00249
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
01/25/2011 VIOL - TENTS, CANOPIES & OTHER dgreenl1 Violation Because canopy has ben converted to a tent, you are required additional safeguards: 1) emergency egress lighting that is activited by the loss of power to primary lighting 2) continuously illuminated EXIT signs over all 3 exits Additionally: the following deficiencies that were not present at the time your permit was approved shall be corrected: 3) Support poles shall be anchored in such a way as to fully support the tent 4) All panels in a tent shall be fire rated - provide proof of fire rating for "billboard" panels or replace with approved ones. 5) Use of liquid fueled kerosene heater is prohibited in tent 6) Generator shall be located at least 10' from tent and shall have adequate clearance from all combustables

Completed Inspections

Case Status: COMPLETE
Case Number: T11FR00249
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/11/2011 INSP - REINSPECTION dgreenl1 Approved Tent has been removed