Inspection Status: Violation
Inspection History: VIOL - TENTS, CANOPIES & OTHER
Case Number - T11FR00249
Inspection Description - VIOL - TENTS, CANOPIES & OTHER
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/25/2011 | VIOL - TENTS, CANOPIES & OTHER | Violation | Because canopy has ben converted to a tent, you are required additional safeguards: 1) emergency egress lighting that is activited by the loss of power to primary lighting 2) continuously illuminated EXIT signs over all 3 exits Additionally: the following deficiencies that were not present at the time your permit was approved shall be corrected: 3) Support poles shall be anchored in such a way as to fully support the tent 4) All panels in a tent shall be fire rated - provide proof of fire rating for "billboard" panels or replace with approved ones. 5) Use of liquid fueled kerosene heater is prohibited in tent 6) Generator shall be located at least 10' from tent and shall have adequate clearance from all combustables |