Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

01/11/2011

Applicant:

SOLAR HOLDINGS LLC

Description:

Full Fire Prevention Inspection. Tina Keene 408-0825

Outstanding Inspections

Case Number: T11FR00093
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
01/11/2011 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. _____1. Remove all storage from obstructing the electrical service equipment located in the back room.
01/11/2011 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Service and test the automatic sprinkler system. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg

Completed Inspections

Case Status: COMPLETE
Case Number: T11FR00093
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
01/31/2011 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.