Case: T11FR00093

Parcel: 10408052D


Addresses:

497 W AUTO MALL DR


Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T11FR00093

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/11/2011 VIOL - BUILDING SVCS & SYSTEMS Correction Required IFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space.

_____1. Remove all storage from obstructing the electrical service equipment located in the back room.