Case Details

Status:

COMPLIAN

Type:

FIRE AT COMMERCIAL BUILDING

Entered Date:

06/24/2011

Applicant:

FOX POINT JOINT VENTURE.ATTN: SCOTIA GROUP MGMT

Description:

APT FIRE UNIT 1313

Outstanding Inspections

Case Number: T11DV04837
Case Status: COMPLIAN
Case Description: FIRE AT COMMERCIAL BUILDING
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
INSP - FOLLOW UP CODE ENFORCE None Not Inspected
08/29/2011 NPO(EL)-MAIN/PANEL/SUB/DISCONT JHURD Item closed
08/29/2011 NPO(EL)-WIRING/SWITCH/OUTLT/FX JHURD Item closed
08/29/2011 NPO(DL)-DILAPIDATED STRUCTURE JHURD Item closed

Completed Inspections

Case Status: COMPLIAN
Case Number: T11DV04837
Case Description: FIRE AT COMMERCIAL BUILDING
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/23/2011 INSP - INITIAL CODE ENFORCMENT JVALDEZ Approved EMERGENCY FIRE CALL; ON SITE INSPECTION RESULTS, FIRE DAMAGE TO THE KITCHEN AREA. THE WALL CAVITY REAR OF THE STOVE HAS BURNT AND BARE CONDUCTORS WHICH POWERED THE EXHAUST FAN ABOVE THE STOVE. THE 220V CABLE TO THE STOVE AND THE WALL RECEPTACLE ARE IN CLOSE PROXIMITY POSSIBLE HEAT DAMAGE. THE DRYWALL IN THIS AREA WAS DAMAGED ESTIMATE OVER 100 SQ FEET. THERE IS SMOKE DAMAGE TO THE INTERIOR OF THE UNIT. THE UNIT #1313 WAS CONDEMNED DUE TO FIRE DAMAGE AND LACK OF POWER. THE ELECTRICAL SYSTEM IS PRIVATE (NOT TEP EQUIPMENT) POWER WAS SHUT OFF AT THE INTERIOR PANEL OF THE UNIT AND THE BUILDINGS MAIN DISCONNECT. PERMITS ARE REQUIRED FOR REPAIRS. UNITS 1309, 1310, 1311, 1319 AND 1320 WERE ALSO EFFECTED WITH NO POWER TO THE UNITS WITH INTERIOR PANEL ON AND MAIN DISCONNECT ON. THE COMPLEX MUST HAVE EITHER A SWITCH GEAR OR TRANSFORMER AND MUST HAVE TRIP OFF. THE ON SITE MANAGER AND MAINTENANCE PERSONAL DID NOT KNOW THE SYSTEM CONFIGURATION. I ORDER TO HAVE THE INTERIOR PANELS AND THE MAIN BREAKER SHUT OFF AS A PRECAUTION. I ADVISED THE MANAGER TO HAVE A LICENSE CONTRACTOR INVESTIGATE THE CONFIGURATION. I ALSO ADVISED TO ALERT ME ONCE WORK HAS BEEN DONE. SCHEDULE A 60 DAY FOLLOW UP INSPECTION WITH AREA INSPECTOR.

Completed Activity Special Conditions

Case Description - FIRE AT COMMERCIAL BUILDING
Case Number - T11DV04837
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 6
Date Name
06/24/2011 CONTACTED IN PERSON
06/24/2011 NOTICE AND ORDER ISSUED
06/27/2011 NOTICE OF VIOLATION ISSUED
08/30/2011 VIOLATION CLOSED
08/30/2011 RESEARCH
06/27/2011 8-5 CITY COMM EMERGENCY

Documents

File Name Document Type  
SKMBT_3700 N. CAMPBELL AVE.PDF DOCUMENTS VIEW