Case: T11DV02047
Case Details
Entered Date:
03/30/2011
Applicant:
WALTER D. & ELEANOR B. RIGGS JT/RS
Description:
Hazardous electrical referred by TFD. TFD responded late last night encountered problem but assessed that issue could wait until next day and cleared scene.
Case Violations
Case Number: T11DV02047
Case Status: COMPLIAN
Case Description: RESIDENTIAL FIRE
Total Violations: 5
| Violation Date | Code Statue |
|---|---|
| 04/01/2011 | T.C. Ch. 16, Sec. 16-4. PERMITS REQUIRED. Unless otherwise exempt pursuant to section 301 of the Administrative Code, as adopted by reference per section 6-1 of this Code, or pursuant to any other ordinance or statute, no building, structure or building service equipment regulated by this chapter or by the technical codes adopted by the city shall be built, erected, constructed, enlarged, altered, repaired, moved, improved, removed, converted or demolished unless a permit first has been obtained from the building official in the manner provided in the administrative and building codes adopted by the city. The purpose of a permit is to ensure that all construction is inspected by qualified City of Tucson personnel as directed by ordinance to verify compliance with city codes. Failure to obtain proper permit with inspections and approvals shall deem the construction to be unsafe. |
| 04/01/2011 | T.C. Ch. 16, Sec. 16-13(b) ACCUMULATION OF REFUSE PROHIBITED. Each owner, lessee, tenant, resident or occupant shall maintain a property so it is free of accumulated refuse and debris. Accumulated refuse and debris means contained or uncontained refuse and debris that is present on the property in a manner not authorized by the Tucson Code. Material recycling facilities meeting the requirements of section 15-24.7 are exempt from this prohibition. |
| 04/01/2011 | T.C. Ch. 16, Sec. 16-12(a)(2) PROTECTIVE TREATMENT. All exterior wood surfaces, except for decay-resistant woods, must be protected from deterioration and from the elements by paint or other protective treatment or covering. Any exterior wood surface that has paint that is peeling, flaking, cracked, blistered or chipped, resulting in bare, unprotected surfaces, the deteriorated condition of that surface must be eliminated and the surface repainted. All metal surfaces subject to corrosion or rust must be treated or coated to inhibit corrosion and rust, unless corrosion or rust is a design element. |
| 04/01/2011 | T.C. Ch. 16, Sec. 16-12(a)(3) BOARDED WINDOW OR DOOR OPENINGS. a. No occupied structure may have boarded window or door openings, except as necessary on a temporary basis to keep the structure secure while under repair. b. While vacant structures may temporarily be secured by boarding up window and door openings in accordance with section 16-14(b), having or maintaining boarded window or door openings on a vacant structure for 180 days or more in any one-year period is prohibited. |
| 04/01/2011 | T.C. Ch. 16, Sec. 16-12(b)(3) ROOFS. The roof of every building or structure shall be maintained in a safe condition and shall provide weather protection for that building or structure. Roof coverings shall not be rotted, broken, split, buckled or otherwise deteriorated. T.C. Ch. 16, Sec. 16-12(b) FOUNDATIONS, WALLS, ROOFS, AND CHIMNEYS. Every foundation, wall, roof, chimney and all exterior surfaces of buildings and structures shall be maintained in structurally sound condition and shall provide weather protection. All wood showing evidence of termite damage or decay, where structural or functional integrity is impaired, shall be replaced. |
Outstanding Inspections
Case Number: T11DV02047
Case Status: COMPLIAN
Case Description: RESIDENTIAL FIRE
Total Outstanding Inspections - 7
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/14/2011 | NPO(EL)-MAIN/PANEL/SUB/DISCONT | JVALDEZ | Item closed | |
| 06/14/2011 | NPO(EL)-WIRING/SWITCH/OUTLT/FX | JVALDEZ | Item closed | |
| 06/14/2011 | NPO(PL)-PLUMBING SYSTEM & FX | JVALDEZ | Item closed | |
| 06/14/2011 | NPO(DL)-DILAPIDATED STRUCTURE | JVALDEZ | Item closed | |
| 06/14/2011 | NPO - REFUSE/TRASH/DEBRIS | JVALDEZ | Item closed | |
| 06/14/2011 | NPO - EXT. BUILDING MAINTENANC | JVALDEZ | Item closed | |
| 06/14/2011 | NPO - INT. BUILDING MAINTENANC | JVALDEZ | Item closed |
Completed Inspections
Case Status: COMPLIAN
Case Number: T11DV02047
Case Description: RESIDENTIAL FIRE
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/30/2011 | INSP - INITIAL CODE ENFORCMENT | JVALDEZ | Approved | 3-29-2011 TFD WAS CALLED OUT TO A HAZARDOUS ELECTRICAL CALL. THE TENNANT STATED HE SMELLED SOMETHING BURNING. ON SITE INSPECTION, FOUND THE EAST PORTION OF THE INTERIOR OF THE HOME IS BEING POWERED BY EXTENSION CORDS COMING FROM THE REAR WEST END OF THE HOME. LIVING, KITCHEN AND BEDROOMS HAVE NEW OPEN JUNCTION BOXES WITH NEW ROMEX CABLES IN THE CEILING AREAS, SOME THE ROOMS HAVE DRYWALL CUT OUTS IN THE CEILING AND WALLS. THE KITCHEN'S CEILING AREA ABOVE THE CEILING JOIST THERE ARE ROMEX CABLES ATTACH BY WIRES NUTS. THE BEDROOM'S CEILING AREA HAS A JUNCTION BOX WITH QUESTIONABLE AMOUNT OF WIRES IN THE BOX, NO COVER PLATE. THESE AREA'S IN THE CEILING LOOK LIKE THE SPLICED CONNECTIONS AND JUNCTION BOXES WILL BE ENCLOSED BY DRYWALL. THE MAIN DISCONNECT HAS NEW BREAKERS, WIRING AND CONDUIT. A 30 AMP BREAKER WITH NUMBER 12 WIRE WAS TRIPPING, THE CIRCUIT WAS UNABLE TO BE TRACE. THE WIRE WAS DISCONNECTED FROM THE BREAKER BY COT. THE MAIN DISCONNECT DOES NOT HAVE A GROUNDING ELECTRODE CONDUCTOR. THERE IS STRAND WIRE WHICH IS BEING USED AS A GROUND JUMPER WIRE FROM THE MAIN DISCONNECT WHICH ENTERS THE NEW SQUARE D PANEL BOARD THEN IS LOOPED TO THE OLD DISCONNECTS BUS BAR WHICH DOES HAVE A GROUNDING ELECTRODE CONDUCTOR TO A ROD. THE NEW SQUARE D PANEL BOARD HAS THE MAIN TERMINALS WHICH ARE DOUBLE LUGGED. THE JUMPER WIRES RUN OVER TO THE OLD DISCONNECT WHICH NOW IS BEING USED AS A PANEL BOARD TO PROVIDE POWER TO THE DWELLING. THE SQUARE D PANEL BOARD HAS 8 NEW CIRCUIT BREAKERS WITH NEW NUMBER 12 ROMEX CABLES WHICH LEADS INTO THE HOME. ONE OF THE CIRCUIT 30 AMP BREAKER IS USING A NUMBER 10 WIRE TO A 15 AMP OUTDOOR RECEPTACLE. THE EXTERIOR OF THE BUILDING HAS AN OPEN JUNCTION BOX WHICH SHOWS CABLES ENTERING THE DWELLING. THERE IS A SECOND GROUNDING ELECTRODE CONDUCTOR WHICH HAS BEEN CUT NEXT TO THE OLD DISCONNECT. ALL THE CIRCUITS IN THE PANEL BOARDS ARE NOT MARKED, IT IS UNKNOWN WHICH CABLES AND DEVICES ARE ENERGIZES IN THE HOME. ALL THE BREAKERS WERE ON THE ON POSITION BUT YET HALF OF THE HOME LACKS POWER. THESE ARE UNAPPROVED WIRING METHODS AND WORK WITH NO PERMITS AND INSPECTIONS. DUE TO THE TAMPERING WITH THE GROUNDING ELECTRODE CONDUCTOR THAT LACKS IN THE DISCONNECT ENCLOSURE AND THE OTHER GROUNDING ELECTRODE CONDUCTOR THAT WAS CUT AND MODIFYING A NEW GROUNDING PATH FOR THE DISCONNECT WITHOUT PERMITS PLUS ALL THE NEW UNAPPROVED WORK THE FIRE CALL FOR ELECTRICAL BURNING SMELL WAS ALSO TAKEN IN CONSIDERATION, THE ONSITE INSPECTION REVEALED THAT THE 30 AMP BREAKER WHEN IN THE ON POSITION IT STARTED TO HUM / BUZZ THIS IS A RESULT OF MIS WIRING POSSIBLE OVER LOADED CIRCUIT. THIS SHOW THE WORK BEING DONE WAS NOT FROM A PROFESSIONAL ELECTRICAL CONTRACTOR. DURING THE INSPECTION A YOUNG GENTLEMEN SHOW UP AND ADMITTED TO ME HE HAD INSTALL 3 NEW CIRCUITS WITHOUT PERMITS BECAUSE HE WAS TOLD THE BOTTOM TWO BREAKER WERE DEFECTIVE. AFTER REVIEWING ALL DATA THE CITY OF TUCSON DID HAVE TEP CUT THE POWER FROM THE POLE. THE DWELLING WAS CONDEMNED UNFIT TO OCCUPY. THE PLACARD WAS POST AND A NOTICE AND ORDER WAS SIGNED BY THE TENANT. OWNER CONTACT WAS NOT MADE AFTER THREE ATTEMPTS. THE PROPERTY DOES ISSUES WITH A TARP THE ROOF, TRASH AND DEBRIS. EXTERIOR WOOD ON THE DWELLING, STORAGE SHED WITH LACK OF PAINT PROTECTION. |
| 06/14/2011 | INSP - FOLLOW UP CODE ENFORCE | JVALDEZ | Approved | ON SITE INSPECTION ALL EXTERIOR VIOLATIONS HAVE BEEN ABATED, THE BUILDING IS SECURED AND HAS A PERIMETER FENCE THAT ALL GATES ARE LOCKED. THE POWER IS CUT FROM THE POLE PERMIT REQUIRED TO ENERIZE, FULL SERVICE UPGRADE IS REQUIRED. OWNER PLAN TO SELL THE PROPERTY. REVIEWED CASE WITH SUPERVISOR AND ADMINISTRATOR AND WILL CLOSE CASE |
Completed Activity Special Conditions
Case Description - RESIDENTIAL FIRE
Case Number - T11DV02047
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 7
| Date | Name |
| 03/30/2011 | CONTACTED BY PHONE |
| 04/01/2011 | CONTACTED IN PERSON |
| 03/30/2011 | RED CROSS / PRIMAVERA |
| 03/30/2011 | NOTICE AND ORDER ISSUED |
| 04/04/2011 | NOTICE OF VIOLATION ISSUED |
| 06/14/2011 | VIOLATION CLOSED |
| 04/04/2011 | 8-5 CITY COMM EMERGENCY |