Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

12/22/2010

Applicant:

DUCA DENNIS TRUST OCT 21, 1992 50%

Description:

FULL INSPECTION

Outstanding Inspections

Case Number: T10FR02713
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
12/22/2010 INSP - FULL JDAVIS Approved 1. _____ 605.5 Extension Cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. - STOCK ROOM -REAR BATHROOM HALLWAY 2. _____ 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. -SOUTHWEST EXIT IN STOCK ROOM (CEILING) - CENTER OF SALES FLOOR (CEILING TILE) - REAR BATHROOM HALLWAY (HOLE IN THE WALL) 3. _____ 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system... - STOCK ROOM - DOOR LEADIGN TO THE STOCKROOM - BATHROOM HALLWAY 4. 001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required by this chapter. The provisions of this chapter shall control the design, construction and arrangement of means of egress components required to provide an approved means of egress from structures and portions thereof... - REPLACE THE MISSIGNN SELF-CLOSURES LEADING TO THE REAR EXIT. 5. _____ 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards. - 5 YEAR CHECK VALVE INSPECTION IS DUE