Inspection History Details
Inspection Status: Correction Required
Inspection History: INSP - FULL
Case Number - T10FR02713
Inspection Description - INSP - FULL
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/13/2011 | INSP - FULL | Correction Required | PRE CIT WRITTEN dECEMBER 22, 2010 | |
01/13/2011 | INSP - FULL | Correction Required | REPORT SENT VIA E-MAIL: Jim- Attached is the report for the Family Dollar Store. Let me know if you need anything else. Thanks. Carrie Gilchirst Cintas Fire Protection 520.884.7979 |
|
12/22/2010 | INSP - FULL | Approved | 1. _____ 605.5 Extension Cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. - STOCK ROOM -REAR BATHROOM HALLWAY 2. _____ 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. -SOUTHWEST EXIT IN STOCK ROOM (CEILING) - CENTER OF SALES FLOOR (CEILING TILE) - REAR BATHROOM HALLWAY (HOLE IN THE WALL) 3. _____ 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system... - STOCK ROOM - DOOR LEADIGN TO THE STOCKROOM - BATHROOM HALLWAY 4. 001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required by this chapter. The provisions of this chapter shall control the design, construction and arrangement of means of egress components required to provide an approved means of egress from structures and portions thereof... - REPLACE THE MISSIGNN SELF-CLOSURES LEADING TO THE REAR EXIT. 5. _____ 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards. - 5 YEAR CHECK VALVE INSPECTION IS DUE |