Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

12/21/2010

Applicant:

TUPART II LLC

Description:

Full inspection done 12/20/2010; Wendy Witzig - Loss Prevention Manager / Jim Matthews- Manager 546-6565 / "M" occupancy.

Outstanding Inspections

Case Number: T10FR02692
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
12/21/2010 INSP - FULL BCOBB Violation Please correct the following Tucson Fire Code violations:
12/21/2010 VIOL - PRECAUTION AGAINST FIRE BCOBB Violation Clearance below sprinklers: TFC 315.2.1 Ceiling clearance. Storage shall be maintained 24 inches (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. ______Remove storage to 18 inches or more below sprinkler head.
12/21/2010 VIOL - MEANS OF EGRESS BCOBB Violation Emergency lighting: IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located] ______Fix all inoperative emergency lights.
12/22/2010 VIOL - BUILDING SVCS & SYSTEMS BCOBB Violation Electrical wires extending through ceiling: TFC2006/ 605.5 Flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors. ______ Please remove wires.
12/22/2010 VIOL - BUILDING SVCS & SYSTEMS BCOBB Violation Multiplug adapters: TFC2006/ 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. ______Remove noncomplying devices.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR02692
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/11/2011 INSP - REINSPECTION BCOBB Approved All approved / closed