Case: T10FR02692

Parcel: 13322424B


Addresses:

7055 E BROADWAY BL


Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T10FR02692

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
12/22/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Electrical wires extending through ceiling:

TFC2006/ 605.5 Flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors.

______ Please remove wires.
12/22/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Multiplug adapters:

TFC2006/ 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.

______Remove noncomplying devices.
12/21/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Extension cords:

TFC2006/ 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.

_____ Remove or replace with approved fused power strip.
12/21/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Open space in electrical panel / Tape on breaker:

TFC2006 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated.

_____Place an approved "blank" in the space.

_______ Remove tape from breakers.