Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

11/16/2010

Applicant:

ST JOSEPHS HOSPITAL OF TUCSON

Description:

RCI systems rpt: System cartridge out of test dated 1988, improper coverage over 2 fryer set has 1 3n for both fryers, fryers need to be protected as 2 fryers not as on big fryer, system also has improper duct coverage duct area not accessible no access doors to cover duct and plenium properly duct nozzle plugged unable to purge- rpt in log book.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR02401
Case Description: INSPECTION
Total Completed Inspections - 1