Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T10FR02401
Case Details
Entered Date:
11/16/2010
Applicant:
ST JOSEPHS HOSPITAL OF TUCSON
Description:
RCI systems rpt: System cartridge out of test dated 1988, improper coverage over 2 fryer set has 1 3n for both fryers, fryers need to be protected as 2 fryers not as on big fryer, system also has improper duct coverage duct area not accessible no access doors to cover duct and plenium properly duct nozzle plugged unable to purge- rpt in log book.
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR02401
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/17/2010 | INSP - FULL | RSPANGLE | Approved | HOSPITAL MAINTENAINCE STAFF DID NOT AGREE WITH CONTRACTORS' INSPECTION REPORT DONE ON OCTOBER25, 2010. THIS HOOD SYSTEM WAS UPGRADED IN APRIL OF 2010. A SECOND CONTRACTOR WAS HIRED TO INSPECT AND HAD NO DEFICIENCIES NOTED ON THE REPORT. THE SECOND REPORT IS ATTACHED TO THE COMPLAINT IN THE LOG BOOK. THIS COMPLAINT IS CLOSED. |