Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

11/10/2010

Applicant:

ORCHARDS AT ARIZONA II LLC

Description:

Full Fire Prevention Inspection. Tony Reed-- 888-2726

Outstanding Inspections

Case Number: T10FR02379
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
11/10/2010 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required IFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly. _____1. Replace the missing ceiling tile located on in the east sales floor area. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
11/10/2010 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. _____1. The portable fire extinguisher located by "Checkout" shall be properly mounted on a hanger or bracket.
11/10/2010 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1.Repair or replace the emergency lighting unit located on the ceiling by the main entrance. _____2. Repair or replace the emergency lighting unit located on the West wall on the sales floor. _____3. Repair or replace the emergency lighting unit located in the North exit hall. _____4. Repair or replace the emergency lighting unit located on the East wall in the sales area.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR02379
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/30/2010 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.