Case: T10FR02379

Parcel: 106060180


Addresses:

1354 W PRINCE RD


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T10FR02379

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
11/10/2010 VIOL - MEANS OF EGRESS Correction Required IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system.

_____1.Repair or replace the emergency lighting unit located on the ceiling by the main entrance.

_____2. Repair or replace the emergency lighting unit located on the West wall on the sales floor.

_____3. Repair or replace the emergency lighting unit located in the North exit hall.

_____4. Repair or replace the emergency lighting unit located on the East wall in the sales area.