Case: T10FR02361
Case Details
Entered Date:
11/08/2010
Applicant:
PARK MU GIL & OAK MAI & PARK GEANIE Y & PARK
Description:
Full Fire Prevention Inspection. Sbeidee Zabalza--- 792-0407
Outstanding Inspections
Case Number: T10FR02361
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/08/2010 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | IFC 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner thatwould prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. _____1. Remove all storage loacted around the " Event Center" sprinkler system riser and control valves. |
| 11/08/2010 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Service and tag the portable fire extinguisher located in the "Bar." _____2. Repair the broken pull station for the kitchen hood extinguishing system. _____3. All cooking equipment loacted under the hood system shall be properly aligned with the extinguishing system nozzles to ensure required system coverage. _____4. Correct all deficiencies noted on the annual sprinkler system inspection done at the "Event Center." |
| 11/08/2010 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. _____1. Clean and remove all grease accumulation from the kitchen hood system. |
| 11/08/2010 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1. Repair or replace the broken emergency lighting unit located on the North wall in the "Event Center Lobby" _____2. Repair or replace the emergency lighting unit in the Women's restroom located in the " Event Center." ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR02361
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/08/2010 | INSP - FULL | JBURGE | Approved | Correct all noted Tucson Fire Code Violations. |