Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

10/28/2010

Applicant:

STANDARD INDUSTRIES

Description:

FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T10FR02274
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
10/28/2010 INSP - FULL WMOTTO Correction Required CORRECT TUCSON CODE VIOLATIONS.
10/28/2010 VIOL - PRECAUTION AGAINST FIRE WMOTTO Correction Required 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. 1___ ALL MATERIAL IN WAREHOUSE NEED TO BE AT LEAST 18 INCHES UNDER SPRINKLER HEADS.
10/28/2010 VIOL - FIRE PROTECTION SYSTEMS WMOTTO Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. 1___ NEED TO PROVIDE A REPORT SHOWING SPRINKLER SYSTEM HAS BEEN SERVICED WITHIN THE YEAR WITH NO DEFICIENCIES. ALL DEFICIENCIES MUST BE REPAIRED FROM THE SPRINKLER REPORT OF 9/24/2009.
10/28/2010 VIOL - MEANS OF EGRESS WMOTTO Correction Required 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1___ NEED TO REMOVE LATCH LOCK ON SOUTH EAST EXIT DOOR IN WAREHOUSE.
10/28/2010 VIOL - MEANS OF EGRESS WMOTTO Correction Required 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. Security devices affecting means of egress shall be subject to approval of the fire code official. 1___ NEED TO REMOVE ALL BOXES FROM INFRONT OF EXIT DOOR ON FAR EAST DOOR IN NOTH WAREHOUSE. 2___ NEED TO REARANGE STOCK IN NORTH EAST WAREHOUSE TO PROVIDE AT LEAST TWO CLEAR PATHS TRAVEL.
10/28/2010 VIOL - MEANS OF EGRESS WMOTTO Correction Required 1028.4 Exit signs. Exit signs shall be installed and maintained in accordance with Section 1011. Decorations, furnishings, equipment or adjacent signage that impairs the visibility of exit signs, creates confusion or prevents identification of the exit shall not be allowed. 1___ NEED TO HAVE ALL EXIT SIGNS IN WAREHOUSE INSPECTED AND REPARIED THAT ARE NOT WORKING. 2___ REPAIR EXIT SIGN BY WATER AND ICE DISPENSER IN MAIN STORE AREA.
10/28/2010 VIOL - LIQUID PETROLEUM GASES WMOTTO Correction Required 3803.2.1 Portable containers. Portable LP-gas containers, as defined in NFPA 58, shall not be used in buildings except as specified in NFPA 58 and Sections 3803.2.1.1 through 3803.2.1.7. 1___ NO PROPONE TANKS CAN BE SORED INSIDE THE BUILDING WITCH CONTAIN PROPANE. ALL TANKS MUST BE STORED OUTSIDE 10 FEET FROM ANY EXIT