Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - PRECAUTION AGAINST FIRE
Case Number - T10FR02274
Inspection Description - VIOL - PRECAUTION AGAINST FIRE
Inspection Status - Correction Required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/28/2010 | VIOL - PRECAUTION AGAINST FIRE | Correction Required | 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. 1___ ALL MATERIAL IN WAREHOUSE NEED TO BE AT LEAST 18 INCHES UNDER SPRINKLER HEADS. |