Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

10/27/2010

Applicant:

ORCHARDS AT ARIZONA II LLC

Description:

Full Fire Prevention Inspection. Alicia Vargas---- 887-0037

Outstanding Inspections

Case Number: T10FR02251
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
10/27/2010 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____1. Remove the extension cord used to power the tamale steamer.
10/27/2010 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____1. All open spaces in the electrical panel located by the northeast EXIT door shall be properly covered. _____2. All open spaces in the electrical panel located in the back stock area shall be properly covered.
10/27/2010 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Service and test the automatic sprinkler system. NOTE: Provide a copy of the inspection report for Fire Department records. _____2. Service and tag the portable fire extinguisher located in the sprinkler riser room. _____3. Replace the missing automatic sprinkler system FDC (Fire Department Connection) inlet cover. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
10/27/2010 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1028.4 Exit signs. Exit signs shall be installed and maintained in accordance with Section 1011. Decorations, furnishings, equipment or adjacent signage that impairs the visibility of exit signs, creates confusion or prevents identification of the exit shall not be allowed. _____1. The EXIT sign located in the back stock room shall be internally illuminated.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR02251
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/18/2010 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.