Case: T10FR02251

Parcel: 106060180


Addresses:

1310 W PRINCE RD


Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T10FR02251

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
10/27/2010 VIOL - BUILDING SVCS & SYSTEMS Correction Required IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.

_____1. All open spaces in the electrical panel located by the northeast EXIT door shall be properly covered.

_____2. All open spaces in the electrical panel located in the back stock area shall be properly covered.
10/27/2010 VIOL - BUILDING SVCS & SYSTEMS Correction Required IFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.

_____1. Remove the extension cord used to power the tamale steamer.