Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

10/15/2010

Applicant:

CITY OF TUCSON

Description:

Old Pueblo Trolley

Outstanding Inspections

Case Number: T10FR02132
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
10/15/2010 INSP - FULL BCORRALE Continued Full inspection of work area used by Old Pueblo Trolley. Independent of the MAITS program.
10/15/2010 INSP - FULL BCORRALE Continued On 10/14 2010, a fire prevention inspection was conducted at the workspace for the Old Pueblo Trolley, 10 N. Park Ave. Please correct the following Tucson Fire Code violations. All code references are from the 2006 International Fire Code, with local modifications.
10/15/2010 VIOL - BUILDING SVCS & SYSTEMS BCORRALE Violation ____Extension cords used in place in place of permanent wiring all throughout repair shop. IFC 2006 605.5 ***UNPLUG CORDS; USE ONLY WITH PORTABLE EQUIPMENT, AND ONLY DURING OPERATION.
10/15/2010 VIOL - FIRE PROTECTION SYSTEMS BCORRALE Violation ____Fire extinguishers overdue for annual test. IFC 2006 901.6 ***SCHEDULE FIRE EXTINGUISHER ANNUAL TEST.
10/15/2010 VIOL - COMPRESSED GASES BCORRALE Violation ____Unsecured gas cylinders. IFC 2006 3003.5.3 ***SECURE CYLINDERS.