Case: T10FR02132
Case Details
Entered Date:
10/15/2010
Applicant:
CITY OF TUCSON
Description:
Old Pueblo Trolley
Outstanding Inspections
Case Number: T10FR02132
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/15/2010 | INSP - FULL | BCORRALE | Continued | Full inspection of work area used by Old Pueblo Trolley. Independent of the MAITS program. |
10/15/2010 | INSP - FULL | BCORRALE | Continued | On 10/14 2010, a fire prevention inspection was conducted at the workspace for the Old Pueblo Trolley, 10 N. Park Ave. Please correct the following Tucson Fire Code violations. All code references are from the 2006 International Fire Code, with local modifications. |
10/15/2010 | VIOL - BUILDING SVCS & SYSTEMS | BCORRALE | Violation | ____Extension cords used in place in place of permanent wiring all throughout repair shop. IFC 2006 605.5 ***UNPLUG CORDS; USE ONLY WITH PORTABLE EQUIPMENT, AND ONLY DURING OPERATION. |
10/15/2010 | VIOL - FIRE PROTECTION SYSTEMS | BCORRALE | Violation | ____Fire extinguishers overdue for annual test. IFC 2006 901.6 ***SCHEDULE FIRE EXTINGUISHER ANNUAL TEST. |
10/15/2010 | VIOL - COMPRESSED GASES | BCORRALE | Violation | ____Unsecured gas cylinders. IFC 2006 3003.5.3 ***SECURE CYLINDERS. |