Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

10/06/2010

Applicant:

RUSTY WAREHOUSE LLC 70% & MC GETTIGAN LIVING TR

Description:

FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T10FR02044
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
10/06/2010 VIOL - BUILDING SVCS & SYSTEMS WMOTTO Correction Required 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. 1___ NEED TO REPAIR ALL OPEN ELECTRICAL BOXES IN SOUTH ROOMS IN BUILDING. 2___ BREAKER PANNEL IN FAR SOUTH ROOM NEEDS BLANKS INSTALLED IN OPEN SLOTS. 3___ J BOX IN SOUTH EQUIPMENT ROOM BEHIND COOLER NEEDS TO BE FIXED.
10/06/2010 VIOL - FIRE PROTECTION SYSTEMS WMOTTO Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. 1___. NEED TO SHOW REPORT SHOWING SPRINKLER SYSTEM HAS BEEN SERVICED AND ALL DEFICIENCIES HAVE BEEN REPAIRED. 2___ NEED TO HAVE CLASS K EXTINGUISHER IN KITCHEN SERVICED AND TAGGED.
10/06/2010 VIOL - FIRE PROTECTION SYSTEMS WMOTTO Correction Required 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. 1__ NEED TO SHOW REPORT THAT HOOD SYSTEM HAS BEEN SERVICED EVERY 6 MONTHS. NEED CURRENT TAG ON SYSTEM AT ALL TIMES.
10/11/2010 VIOL - MEANS OF EGRESS WMOTTO Correction Required 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 1. Places of detention or restraint. 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F,M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: 2.1. The locking device is readily distinguishable as locked, 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, 2.3. The use of the key-operated locking device is revocable by the fire code official for due cause. 3. Where egress doors are used in pairs, approved automatic flush bolts shall be permitted to be used, provided that the door leaf having the automatic flush bolts has no doorknob or surface- mounted hardware. 4. Doors from individual dwelling or sleeping units of Group R occupancies having an occupant load of 10 or less are permitted to be equipped with a night latch, dead bolt or security chain, provided such devices are openable from the inside without the use of a key or tool. 1___ SLIDING DOOR NEEDS TO HAVE A SIGN AT EYE LEVEL STATING DOOR IS TO REMAIN IN OPEN POSITION WHEN OCCUPIED.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR02044
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/24/2010 INSP - FULL WMOTTO Approved ALL VIOLATIONS ABATED. PRE CITE STILL IN PROGRESS AWAITING PERMITS FOR BACK ROOM BEFORE THEY CONTINUE WORK.