Case: T10FR02044

Parcel: 124150070


Addresses:

800 E 16TH ST


Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T10FR02044

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
10/06/2010 VIOL - FIRE PROTECTION SYSTEMS Correction Required 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion.

1__ NEED TO SHOW REPORT THAT HOOD SYSTEM HAS BEEN SERVICED EVERY 6 MONTHS. NEED CURRENT TAG ON SYSTEM AT ALL TIMES.
10/06/2010 VIOL - FIRE PROTECTION SYSTEMS Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.

1___. NEED TO SHOW REPORT SHOWING SPRINKLER SYSTEM HAS BEEN SERVICED AND ALL DEFICIENCIES HAVE BEEN REPAIRED.

2___ NEED TO HAVE CLASS K EXTINGUISHER IN KITCHEN SERVICED AND TAGGED.