Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

09/29/2010

Applicant:

SMITH FAMILY REAL ESTATE INVESTORS LTD

Description:

AST

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR01984
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
09/29/2010 INSP - AST CFUNKE Approved Requirements met. Permit Issued
09/29/2010 INSP - AST CFUNKE Approved The tanks on your property must have a permit obtained through the City of Tucson. Below are the codes that require the permit and give the requirements for installation. 3404.2.7.3.3 Vent pipe outlets. Vent outlets on atmospheric tanks storing Class IIIB liquids are allowed to discharge inside a building if the vent is a normally closed vent. " Install the required vents, if the tanks are indoors install the "Normally closed or Pressure/ vacuum" type vent 3404.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires. The venting shall be installed and maintained in accordance with Section 2.2.5.2 of NFPA 30. " Install the required emergency vents.