Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Continued
Inspection History: INSP - AST
Case Number - T10FR01984
Inspection Description - INSP - AST
Inspection Status - Continued
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/29/2010 | INSP - AST | Continued | The tanks on your property must have a permit obtained through the City of Tucson. Below are the codes that require the permit and give the requirements for installation. 3404.2.7.3.3 Vent pipe outlets. Vent outlets on atmospheric tanks storing Class IIIB liquids are allowed to discharge inside a building if the vent is a normally closed vent. " Install the required vents, if the tanks are indoors install the "Normally closed or Pressure/ vacuum" type vent 3404.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires. The venting shall be installed and maintained in accordance with Section 2.2.5.2 of NFPA 30. " Install the required emergency vents. |
|
09/29/2010 | INSP - AST | Approved | Requirements met. Permit Issued |